1. GENERAL
1.1. WARNINGS
This manual provides information and instructions for the correct lifting, installation, operation and maintenance of this
fan series.
The manufacturer; Soler & Palau Sistemas de Ventilación S.L.U. accepts no responsibility for costs, breakages, acci-
dents or any inconvenience caused by failure to comply with the instructions contained in this manual, general codes
of practice or due to improper use.
The units referred to in this manual have been manufactured in accordance with rigorous quality control and interna-
tional standards.
This instruction manual contains important information and must be read carefully by competent persons prior to any
handling, transport, inspection or installation of this product. Every care has been taken in the preparation of the ins-
tructions and information, however, it is the responsibility of the installer to ensure the system complies with relevant
national and international regulations, especially safety.
The purchaser, installer, user is responsible for ensuring that the unit is installed, operated and serviced by competent
and qualifi ed personnel, acting in accordance with all safety precautions applicable and as required by law, regulations
and standards in the country applicable.
This unit is designed and manufactured in accordance with EC Machinery Directive 2006/42/EC. Safety guard and other
accessories are available from S&P if required due to specifi c installation.
This unit is designed for use in standard atmospheric conditions as defi ned in IEC 60079-0, and clean ambient air or
ducted air conditions within, -5°C to +50°C, unless stated otherwise.
S&P manufactures various fan equipment with a sourced / sub-supplier motor
. Only S&P supplied spare parts are to
be used for all fans.
For “high temperature” fans, no modifi cation or repair may be made, without prior agreement with manufacturer,
especially with regard to motor, gap between rotating parts / impeller and fi xed fan parts / casing, as well as the
HATCH opening system. Doing so may result in void warranty.
Any work including transport, installation, inspection, maintenance, service spares replacement, repair and fi nal end of
life disposal must be carried out by competent persons and supervised by competent executive.
EC declaration of conformity is available as separate documentation to the fan product.
This Instruction manual is subject to modifi cations due to further technical developments of the fan described, images
and drawings may be simplifi ed representations. Due to improvements and modifi cations the fan operated may differ
from the representations.
S&P reserve the right to vary the product without prior notice.
1.2. SAFETY INSTRUCTIONS
Safety on site is responsibility of competent personnel and in accordance with applicable International, National and
Local regulations. This unit should be electrically isolated and locked out before any work started.
• Safety guard accessories are available from S&P if required due to specifi c installation.
• Safety protective clothing, equipment, hearing protection, and tools may be required.
Safe selection
• Fan equipment shall be selected based on competent users / employers / competent person, data.
• User’s electrical supply, air duty, and any relevant data, for example if speed control is required, must be considered.
• All fan data applicable to “Standard Air” with inside ambient air / ducted air temperature within range, -5°C to +50°C
unless stated otherwise.
Safe ventilation
• Ensure adequate ventilation available to fan and motor. Working ambient inner temperature for this fan series should
not be exceeded, typically this will be within -5°C to +50°C, unless stated otherwise.
Safe operation
• This emergency ventilation fan and motors are suitable for S1 duty cycle, and one off emergency smoke operation
(dual purpose). The fan motor power supply must be designed to accommodate any motor protection devices, where
applicable, for S1 duty cycle. Ensure these devices are fi tted and operating correctly.
However, for emergency smoke extract the fan is designed and certifi ed to run at the stated temperature and time, or
to destruction. Therefore, all motor protection devices must be disabled or bypassed under such event.
Power supply should be via a protected source to enable fan to run under emergency fi re smoke conditions. In case a
VSD is used for normal ventilation, it shall be bypassed in this scenario, leaving the fan in Direct on line supply.
• If fan is not to be operated for long periods of time, it should be run as prescribed by local regulations, or as minimum
15 minutes each month, to ensure safe operation.