58
ENGLISH
GND
24 V
A
C
14-28 VDC
0-10V / 2-10V
4-20 mA / 0-20 mA
Pressure
Connection
CONSTANT PRESSURE OPERATION
• Configure the micro switch DIP 1 of SW1 to obtain an output signal (0-10V).
SW1
OUTPUT
DIP1
TERMINAL
0-10V
OFF
Terminal 2
2-10V
ON
0-20mA
OFF
Terminal 4
4-20mA
ON
• Configure the SW2 selector as indicated in the tables below.
PTH_3202 - SW2 position
PRESSURE RANGE
SW2
-50..+50 Pa
0=On
0..+100 Pa
1=On
0..+150 Pa
2=On
0..+300 Pa
3=On
0..+500 Pa
4=On
0..+1.000 Pa
5=On
0..+1.600 Pa
6=On
0..+2.500 Pa
7=On
POSITION 8-
%
F==..+25000 PA