57
ENGLISH
Menu
Parameter
Value
drC
SFr
8 kHz
I-O
tCC
2C
I-O
tCt
LEL
I-O
rrS
nO
Set
LSP
20 Hz
FUn
PSS
PS2
nO
FUn
PSS
PS4
nO
FUn
SAI
SA2
nO
FUn
PI
PIF
AI1
FUn
PI
rPG
0,2
FUn
PI
rIG
0,2
FUn
PI
PII
YES
FUn
PI
rPI
50,0
FUn
StC
Stt
nSt
FUn
AdC
AdC
nO
Enter the rated values from the name plate for the motor used in the parameters shown in the
table below:
WarNING: where using a single frequency inverter to control two motors,
double the value of the rated current “nCr”
Menu
Parameter
Notes
drC
bFr
Rated frequency of the fan
drC
UnS
Rated voltage of the motor as shown
on the name plate
drC
FrS
Rated frequency of the motor as shown
on the name plate
drC
nCr
Rated current of the motor as it appears
on the name plate
drC
nSP
Rated speed of the motor as shown
on the name plate
drC
COS
Cosine of the phase offset angle of the motor
as shown on the name plate
Finally again press “ESC” for two seconds until the 3 indicator LEDs light sequentially to return