background image

Merlin 1000V

    

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

S&S Northern Ltd

  

5  

 

Pressure Low LED  

 Under normal working conditions the LED is off. The LED will illuminate AMBER when 

pressure of the gas supply drops below 12mBar for 10 secs. The gas valve will close. (The 
system will only go to pressure low from gas on). 

 OFF = OK  
 AMBER = gas supply pressure low.  

 

   Timeout LED 

 

   Under normal working conditions this LED is off. This LED will illuminate AMBER when     

 

   auto-shut down has occurred. 

  

   OFF = OK 

    

   AMBER = auto-shut down 

 

EM Stop LED  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will 

illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before 
restarting the system. 

OFF = OK  

AMBER = EM Stop button pressed  

 

CO2/Gas Detected LED  

Under normal working conditions this LED is off. If the external Merlin detector/ CO2 

connected detects gas this will show RED and the Gas valve will turn off. 

OFF = OK  

RED = Gas detected / high ppm levels of CO2 

 

Fan Fault LED 

Under normal working conditions this LED is off. If a fan fault is present for more than 10 

seconds, the LED will illuminate RED. The system will only go into fan fault from gas on.

 

OFF = OK  

RED = the gas supply has been shut off due to a ventilation fault.  

WHEN A FAULT IS PRESENT YOU WILL NEED TO CONTACT YOUR 

SERVICE/MAINTENANCE COMPANY. 

 

YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR OR RECTIFY THE FAULTS 

UNLESS YOU ARE QUALIFIED TO DO SO.  

 

3.3 

Using the emergency shut off  

The Emergency shut off button is located on the front of the panel.        

There is also a facility for remote shut off buttons to be wired in series.   
The Emergency shut off button(s) will cut off the gas supply when activated.To  

reinstate the system, the Emergency shut off button(s) will need to be reset and the panel 

restarted.  

 

3.4 

BMS integration 

The Merlin 1000V can be integrated with a BMS to make or break a circuit on gas      

on/gas off, (valve open or valve closed). This will tell the BMS whether or not the room  
has use of the gas supply.  

There is a dip-switch located on the inside facia of the Merlin 1000V 

labelled ‘BMS    

Selection’. This is factory set in the ‘off’ position which signals the BMS on gas on/gas  
off. When swit

ched to the ‘on’ position, the 1000V will only signal the BMS on a  

fault, i.e. CO2 high level detected, gas detected, EM Stop pressed, etc.  

 

Summary of Contents for Merlin 1000V

Page 1: ...Merlin 1000V Product Data Sheet S S Northern Ltd 1 Gas Safety Products Merlin 1000V Gas Proving Ventilation Interlocking System Installation operating and maintenance 13 02 2017...

Page 2: ...tected 4 2 9 FS 123 4 2 10 Fan PD Switch 4 2 11 12v DC 4 2 12 Internal Buzzer 4 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 Power LED 4 Gas on LE...

Page 3: ...fused at 3 Amps 2 4 BMS Connections Terminal connections are available on the circuit board for connections to Building Management systems etc Detailed on the circuit board as BMS N C Com and N O the...

Page 4: ...de using a screened cable to avoid electrical interference should not be in the same conduit as per the low voltage directive 3 Operation Instructions 3 1 How to turn the system on and off 1 Turn off...

Page 5: ...or more than 10 seconds the LED will illuminate RED The system will only go into fan fault from gas on OFF OK RED the gas supply has been shut off due to a ventilation fault WHEN A FAULT IS PRESENT YO...

Page 6: ...tallation this can be switched to the on position if required This will instruct the system to leave the fans on and only shut off the gas supply on activation of the Emergency shut off button s Note...

Page 7: ...buttons and Fire Alarm input wired in series purchased separately VOLT FREE INPUT 10 Methane CO or LPG Detector power supply and volt free input purchased separately CO2 Monitor purchased separately...

Page 8: ...ww snsnorthern com info snsnorthern com South East Division Tel 44 0 1702 291 725 Fax 44 0 1702 299 148 south snsnorthern com Rev Date Author Description 01 13 02 2017 S S Northern BT Merlin 1000V Pro...

Reviews: