Merlin GDP4

 

 

 

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

Rev: 05 Date: 08-01-18

  

3  

General information  

The Merlin GDP4 is a multi-zone gas detection panel which can be used in many applications, e.g. 
factories, car parks, shopping centres and the most common being a boiler house application. The 
GDP4 can be used with up to 12 gas detectors wired in parallel (maximum 3 detectors per zone). 

 

Many varieties of detectors are compatible with GDP4, e.g. Natural Gas, Carbon Monoxide, LPG and 
Oxygen depletion. These detectors can be used in any combination. Also multiple thermal links can be 
used, when wired in series. The GDP4 can be integrated with a BMS, fire alarm and remote emergency 
shut-off buttons.  

 

 Installation 

2.1 

Panel Mounting 

The control panel is designed for surface mounting using 4 mounting screws.                                  

Removing the cover on the panel gives access to the circuit board. 

2.2 

Mains Supply 

A 230VAC electrical supply should be supplied to the panel. This should be 

externally fused at 3 Amps using a fused spur and should be con

nected to the terminals marked ”LNE 

Power

 

2.3 

Gas solenoid valve 

The gas solenoid valve should be powered using the terminals on the 

Merlin GDP4 

marked “LNE GAS VALVE”. 

2.4 

Gas Detector 

The terminals detailed on the circuit board as “Gas Detector Zone 1”, “Gas 

Detector Zone 2”, “Gas Detector Zone 3” & “Gas Detector Zone 4”. These connections are “+,-“ and 
”CL” and can be wired to a Merlin gas detector. Natural gas, Carbon monoxide or LPG. Other detector 
types are available. 

 

2.5 

Remote emergency shut off buttons 

The terminal for remote emergency shut-off buttons is 

detailed 

on the circuit board as “EM REMOTE”. These connections are linked out as a factory setting. 

Remote emergency shut-off buttons should be volt free and wired to the Merlin GDP4 using two-core 
cable. 

2.6 

Heat Detector 

The terminal for heat detectors is detailed on 

the circuit board as “HEAT    

SENSOR”. These connections are linked out as a factory setting. Heat detectors should be volt free and 
wired to the Merlin GDP4 using two-core cable. 

2.7 

Fire Alarm 

The terminal for fire alarms is detailed on the circuit board as “FIRE PANEL”.    

These connections are linked out as a factory setting. Fire alarms should be volt free and wired     to 
the Merlin GDP4 using two-core cable.

 

2.8 

BMS Connections 

Terminal connections are available on the circuit board for connections to 

Building Management systems etc. Detailed on the ci

rcuit board as “BMS OUT N/C, COM and N/O” 

these are volt free connections. 

 

2.9 

Sounder Alarm 

The terminal for sounder alarms is detailed on the circuit board as  

  

“SOUNDER/STROBE”. Sounder alarms should be wired using low voltage cable and wired to the Merlin 
GDP4 using two-core cable. This terminal has a 24VDC output.

 

2.10 

Internal Buzzer 

Operates at 90dB measured 30cm from closed panel. 

2.11 

Mute 

The button on the front fascia of the panel detailed "MUTE”, mutes the internal buzzer. 

 

 

 

Note: all low voltage connections should be made using a screened cable. To avoid electrical 
interference this should not be in the same conduit as mains cable as per the low voltage 
directive.

 

 

Summary of Contents for Merlin GDP4

Page 1: ...Merlin GDP4 Product Data Sheet Rev 05 Date 08 01 18 1 Gas Safety Products Merlin GDP4 Installation operating and maintenance Read these instructions carefully before operating or servicing...

Page 2: ...8 BMS Connections 3 2 9 Sounder Alarm 3 2 10 Internal Buzzer 3 2 11 Mute 3 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 3 2 1 Power LED 4 3 2 2 G...

Page 3: ...G Other detector types are available 2 5 Remote emergency shut off buttons The terminal for remote emergency shut off buttons is detailed on the circuit board as EM REMOTE These connections are linked...

Page 4: ...as On OFF Gas Off 3 2 3 EM Stop LED If an emergency shut off button either remote or on the panel is pressed the LED will illuminate AMBER and the gas will be turned off The EM Stop button must be re...

Page 5: ...ther or not 230V is being sent to the solenoid There is a dip switch located on the inside facia of the Merlin GDP4 labelled BMS SEL This is factory set in the off position which signals the BMS on ga...

Page 6: ...DC power supply purchased separately 7 Remote EM Stop buttons purchased separately VOLT FREE INPUT 8 Fusible Links purchased separately VOLT FREE INPUT 9 Fire panel Supplied by others VOLT FREE INPUT...

Page 7: ...l household waste but kept separate for the treatment recovery and recycling of the materials used Please contact your supplier or local authority for details of recycling schemes in your area CONTACT...

Reviews: