Merlin PM2+     

 

 

 

                                                                               User Guide  

 

 

Rev: 2   05-19

 

4  

2

 

Circuit Board Terminals 

 
 

2.1

 

POWER 

A 12v DC electrical supply should be supplied using the [+ - 12/24 VDC 
Power]. 
 
 
 

 
2.2

 

FAN 1 & FAN 2 LIVE – Current monitoring  

Located at the bottom of the main circuit board there are two 
terminals for fan current monitoring, and these are marked up as [FAN 
1 LIVE IN / OUT] & [FAN 2 LIVE IN / OUT].  
The live feed from the fan speed controller should be taken through  
these contacts. Each will monitor its own independent fan.  
From a fan controller the live feed should be taken to the [IN] terminal 
and the [OUT] terminal should wire to the fan motor. 
 

Merlin panels 1500S / 2000S are sent from the factory with links in the terminals marked [SUPPLY 
FAN PD SWITCHES & EXTRACT FAN PD SWITCHES] & [FAN1 PD SW & FAN2 PD SW]. If only one fan 
is being monitored the relevant link should be taken out of the terminal connection.  

 
These terminals are low volt only. 
 
 
 
 
 
If both fans are being monitored – both links should be removed 

and a connection should be supplied to the terminals marked on 
the Merlin PM2+ panel [FAN PDS OUT].  

 
 
 

 

There is an option to set a minimum and maximum running current for the fans to operate on.

 

If 

the current goes above the or below these parameters the PM2+ will switch relay for NC 
(normally closed) to NO (normally open) for relevant [FAN# PDS OUT] and on the main Merlin 
panel the relevant supply/ extract fans LED will begin to flash for ~10 seconds before the Fan 
Fault alarm will be illuminated and the gas solenoid valve connected will be isolated.

 

 
 
For more information see section 3 –‘How to set up the current monitors’. 
 
 
 

Summary of Contents for Merlin PM2+

Page 1: ...Merlin PM2 User Guide Rev 2 05 19 1 Gas Safety Products Merlin PM2 Dual Current Monitor User Guide Please read this guide carefully and retain for future use...

Page 2: ...ting 3 2 Circuit Board Terminals 4 2 1 POWER 4 2 2 FAN 1 FAN 2 LIVE Current monitoring 4 3 How to setup the current monitors 5 3 1 Setting the minimum maximum fan current 5 3 2 How to adjust the curre...

Page 3: ...surface mounting using 4 mounting screws Removing the cover on the panel gives access to the circuit board Important Warning Statements Never ignore your device when in alarm This device requires a c...

Page 4: ...ed SUPPLY FAN PD SWITCHES EXTRACT FAN PD SWITCHES FAN1 PD SW FAN2 PD SW If only one fan is being monitored the relevant link should be taken out of the terminal connection These terminals are low volt...

Page 5: ...will be isolated To adjust this threshold see following section To erase the calibration data press and hold the relevant RESET button until appears 3 2 How to adjust the current monitor thresholds Th...

Page 6: ...Once Fan 1 threshold has been set the LCD screen will prompt setting fan 2 Offset H F2 10 Once you have completed setting the thresholds switch F1 and F2 switches to ON You will now need to calibrate...

Page 7: ...FREE OUTPUT to Merlin panel PD SWITCH terminal 3 POWER IN 12 24 VDC 4 FAN 2 NO NC VOLT FREE OUTPUT to Merlin panel PD SWITCH terminal 5 FAN 2 IN OUT MAX 18AMPS 6 Fan Current Monitor High Button 7 Fan...

Page 8: ...able for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a br...

Reviews: