How to setup the current monitors  

 

 

3.1

 

Setting the minimum & maximum fan current.  

 

 

Turn Fan 1 (F1) switch to ON position.  

 

The LCD screen will show Fan 1 current. 

! - means Fan1 has not yet been calibrated. 

 

 

Set Fan 1 minimum operating current.  

 

Press and hold the F1 LOW button. 

 

LCD screen will display: F1 LOW SAVED. 
 

 

Set Fan 1 maximum operating current. 

 

Press and hold the F1 HIGH button. 

 

LCD screen will display: F1 HIGH SAVED. 

  Please repeat steps to set min & max current of Fan 2. 
 

  IF YOU ARE ONLY INTERLOCKING WITH ONE FAN, PLEASE LEAVE THE REMAINING [F] SWITCH 

TO THE ‘1’ or ‘OFF’ POSITION TO PREVENT NUISANCE TRIPPING. 

If the measured current falls below or rises above 10% of the permitted current, the LCD display 
will show a ‘LOW!‘ or ‘HIGH!’ message next to the relevant fan and the gas solenoid valve 
connected will be isolated. To adjust this threshold – see following section. 

 

To erase the calibration data press and hold the relevant [RESET] button until ‘!’ appears. 

 

 

3.2

 

How to adjust the current monitor thresholds. 

The PM2+ has a factory set 10% dropout threshold for low and high values for both fans. 
However, it is possible to alter between a 10% to a 40% dropout threshold if required.  

Follow these instructions 

1.

 

Switch F1 and F2 switch OFF. 

2.

 

LCD will display ‘F1 and F2 OFF’ 

3.

 

To change the LOW threshold, press and hold F1 and F2 LOW buttons together  

4.

 

The LCD screen will display ‘Offset L  F1 10%’  

5.

 

Select different thresholds by pressing the F1 LOW button  

6.

 

After 5 seconds of inactivity the LCD screen will display the new low offset value for F1 (fan 1). 

7.

 

Once Fan 1 threshold has been set the LCD screen will prompt setting fan 2 ‘Offset L F2 10%’. 

8.

 

Repeat step 4, 5, 6 as above for Fan 2.  

9.

 

Once this has been setup the LCD screen will display the new low offset value for F2 (fan 2). 
 
 
 
 
 
 

F1! 10.0A 
F2 OFF 

F1 LOW 
SAVED 

F1 HIGH 
SAVED 

F1 LOW! 

F2 10.5A 

Summary of Contents for Merlin PM2+

Page 1: ...Merlin PM2 User Guide Rev 2 05 19 1 Gas Safety Products Merlin PM2 Dual Current Monitor User Guide Please read this guide carefully and retain for future use...

Page 2: ...ting 3 2 Circuit Board Terminals 4 2 1 POWER 4 2 2 FAN 1 FAN 2 LIVE Current monitoring 4 3 How to setup the current monitors 5 3 1 Setting the minimum maximum fan current 5 3 2 How to adjust the curre...

Page 3: ...surface mounting using 4 mounting screws Removing the cover on the panel gives access to the circuit board Important Warning Statements Never ignore your device when in alarm This device requires a c...

Page 4: ...ed SUPPLY FAN PD SWITCHES EXTRACT FAN PD SWITCHES FAN1 PD SW FAN2 PD SW If only one fan is being monitored the relevant link should be taken out of the terminal connection These terminals are low volt...

Page 5: ...will be isolated To adjust this threshold see following section To erase the calibration data press and hold the relevant RESET button until appears 3 2 How to adjust the current monitor thresholds Th...

Page 6: ...Once Fan 1 threshold has been set the LCD screen will prompt setting fan 2 Offset H F2 10 Once you have completed setting the thresholds switch F1 and F2 switches to ON You will now need to calibrate...

Page 7: ...FREE OUTPUT to Merlin panel PD SWITCH terminal 3 POWER IN 12 24 VDC 4 FAN 2 NO NC VOLT FREE OUTPUT to Merlin panel PD SWITCH terminal 5 FAN 2 IN OUT MAX 18AMPS 6 Fan Current Monitor High Button 7 Fan...

Page 8: ...able for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a br...

Reviews: