The 

Sanitaire

®

Room Air Sanitizers Model RSCS280 are fitted with a permanent, washable, electrostatic air 

filter. 

DO NOT

apply oil, or adhesive sprays to the filter.

In most applications, regular vacuuming will maintain peak performance of electrostatic filter; periodically flushing
electrostatic filter with clean water is recommended whenever vacuuming fails to restore a clean appearance.

The electrostatic filter may be cleaned repeatedly without loss of efficiency. The frequency of cleaning will vary 
with the conditions surrounding each installation.

C

LEANING OF

E

LECTROSTATIC

F

ILTER

WARNING:

Always disconnect power to the fixture before performing  any service or maintenance.

1.

Disconnect power to the fixture.

2.

Unlatch and remove access cover.

3.

Remove filter from the housing.

4.

Vacuum the upstream side first, and repeat on the discharge side. (Skip to step 7 unless washing filter.)

CAUTION:

Do not use a high velocity water stream to clean the filter. A high velocity stream may 

destroy the filter's internal fibers.

5.

To wash filter, flush thoroughly with clean water, either by immersing or with a fine spray in the direction 
opposite to the airflow. If the filter is contaminated with heavy grease concentrations, wash filter with a 
detergent solution. 

NOTE:

Follow all manufacturer's instructions and precautions for handling detergents. The 

filter should be rinsed thoroughly with clean water. 

6.

Shake off any excess water from filter and let dry.

7.

Replace filter into the housing, with airflow direction label pointing into the electrical enclosure.

8.

Close and re-latch access louver.

9.

Restore power to the fixture.

10. Verify operation by viewing Lamp Operation Indicators (LEDs). If the sanitizer is not operating properly, go to 

Troubleshooting

” section on page 10.

B

REAKAGE

CAUTION:

Broken Quartz is SHARP.

Wear protective gloves when handling broken ultraviolet lamps.

In the event of breakage, 

DO NOT use a household vacuum cleaner to pick up fragments of the lamp. 

Sweep up debris into a plastic bag and dispose of properly.

D

ISPOSAL OF

M

ERCURY

A

DDED

L

AMPS

Germicidal ultraviolet lamps, like standard fluorescent lamps contain small amounts of mercury. Mercury added 
lamps should not be placed in the trash. Dispose of properly.
For further information regarding the disposal and recycling of lamps containing mercury, along with Federal and State
requirements visit http://www.lamprecycle.org. Product Data Sheets for germicidal ultraviolet lamps can be found in the
“PDF Library for

Ster-L-Ray

®

Germicidal Ultraviolet Lamps” section of http://www.ultraviolet.com.

!

!

!

Summary of Contents for RSCS280

Page 1: ...evised January 2011 2003 2011 Atlantic Ultraviolet Corporation ultraviolet com 375 Marcus Boulevard Hauppauge NY 11788 USA 631 273 0500 Fax 631 273 0771 e mail info ultraviolet com Extensive Product Information Available at ...

Page 2: ...r Model RSCS280 Questions that are not specifically answered by these instructions should be directed to the Factory Atlantic Ultraviolet Corporation takes all possible precautions when packaging equipment to prevent damage Carefully inspect and report all damages immediately Do not install damaged equipment Follow all instructions on any labels or tags Carefully inspect all packing materials befo...

Page 3: ...l is used to identify an ULTRAVIOLET LIGHT hazard This symbol pictorial is used to identify the need to wear approved ultraviolet resistant face shield This symbol pictorial is used to identify the need to wear protective gloves SAFETY INSTRUCTIONS WARNING To guard against injury basic safety precautions should be observed including the following 1 Read and follow ALL safety instructions WARNING A...

Page 4: ...perates on 120VAC 60Hz single phase standard household current is standard in most units The Sanitaire is also available for operation on 230VAC 50Hz Permanent washable electrostatic intake filter capable of removing airborne particles as small as 5 microns A louvered exhaust which restricts ultraviolet radiation from passing into the room protecting the room s occupants from ultraviolet exposure ...

Page 5: ...ess steel frame Access to the lamp exposure chamber is gained through the interlocked access door Fixture operation can be monitored from the base panel The operation of the Sanitaire Room Air Sanitizer Model RSCS280 is as follows 1 Air is drawn into the fixture through the the louvered filter panel 2 LED indicator lights provide positive indication of operation of germicidal ultraviolet lamps 3 T...

Page 6: ...ected Germicidal lamps are packed separately to ensure maximum protection for the lamps Keep the lamps aside until ready for installation Carefully inspect all packing materials to prevent the loss of accessories mounting hardware spare parts or instructions Do not discard packing materials until fixture is assembled and check out is complete The Sanitaire Model RSCS280 Room Air Sanitizer includes...

Page 7: ...y from any one of these suspension points unit weight can be found in the equipment specification Avoid using a single cable or chain or other structural element to support more than one suspension point Never attempt to support or suspend this unit on the ceiling tile track system Remember it is the equipment user s responsibility to insure an adequate and safe installation of this equipment and ...

Page 8: ... or maintenance LAMP INSTALLATION REPLACEMENT OR CLEANING WARNING Always disconnect power to the fixture before performing any service or maintenance CAUTION Ultraviolet lamps are easily damaged and may cause injury if broken Exercise care when handling lamps 1 Disconnect power to the fixture 2 Open access door by unlocking the two 2 latches 3 Remove lamps carefully press lamp against the spring l...

Page 9: ... contaminated with heavy grease concentrations wash filter with a detergent solution NOTE Follow all manufacturer s instructions and precautions for handling detergents The filter should be rinsed thoroughly with clean water 6 Shake off any excess water from filter and let dry 7 Replace filter into the housing with airflow direction label pointing into the electrical enclosure 8 Close and re latch...

Page 10: ...nctioning Locate corresponding ballast and replace All germicidal lamps Lamps not installed Install lamps not operating Interlock switch open Confirm access cover is on and latched Interlock switch faulty Replace interlock switch 1 ArmorLite Safety Shield Protective coating applied to Ster L Ray Lamps Insures protection by eliminating the dangers associated with fragments of broken quartz and merc...

Page 11: ...ic Feet per Minute 280 Nominal Fixture Capacityc Cubic Feet per Minute 210 Max Treatment Capacity Cubic Feet per Hour 12 600 Max Room Size 3 Air Changes Hour Cubic Feet 4 200 Max Room Size 4 Air Changes Hour Cubic Feet 3 150 Max Room Size 5 Air Changes Hour Cubic Feet 2 520 Max Room Size 6 Air Changes Hour Cubic Feet 2 100 Dimensions Length Inches 46 5 8 Width Inches 22 1 8 Height Inches 9 7 16 El...

Page 12: ...has been made to determine the patent status of applications illustrated or described in this publi cation Inclusion in this publication of any design or method of use which may be patented is not to be con strued as promoting or sanctioning unauthorized use USER ASSISTANCE Purchased From Date Model Serial No Atlantic Ultraviolet Corporation makes every effort to ensure that the Sanitaire Room Air...