39
Code
Function name
Setting range
Increment
Unit
Default
value
Changeable
during
operation
F000
Rated current
setting
1
to 9999
1
A
*1
✓
F001
Rated voltage
setting
0.1
to 999.9
0.1
V
*2
✓
(*1: Differs according to the unit model.)
(*2: 200.0 or 400.0 according to the unit model.)
Rated value setting
The output current, output voltage, and output power displayed in MONITOR mode are
converted on the basis of [F000] and [F001]. To display them correctly, you must set the
rated values according to the usage conditions. Appropriate values differ according to the
usage status of optional items. See the following table to set the values.
Conversion board to
use
CT to use
Rated current
setting
Rated voltage
setting
[F408]
[F407]
[F000]
[F001]
None
Built-in CT
(1)
(3)
UG-TB1A
Built-in CT
(1)
(3)
External CT
(optional item)
(2)
(3)
UG-TB1V
Built-in CT
(1)
(4)
UG-TB3
Built-in CT
(1)
(4)
UG-TB3U
UG-TB3H
External CT
(2)
(4)
UG-TB3HU
(optional item)
UG-TB4
External CT
(2)
(4)
UG-TB4H
(optional item)
(1) Set the rated current to that specified for the unit model.
(2) Set the rated current to that specified for the primary side of the main circuit CT. (The
value indicated with ■■ in the following figure)
(3) Set the rated voltage to that calculated with the following formula.
Voltage = Main circuit input voltage ×
200
Control circuit input voltage