88
Item
Specifications
Conversion
board
Heater
disconnection
detection
(standard
version)
Load to apply
Heaters with a constant resistance
Disconnection
detectable range
Output voltage and current that are
10% of the ratings or higher
Maximum number of
parallel-connected
loads
20
Heater
disconnection
detection (highly
functional
version)
Load to apply
Heaters with variable resistance
Disconnection
detectable range
Output current that is 30% of the
rating or higher
Maximum number of
parallel-connected
loads
10
External
PT
*
For 110 V
Rated primary input
110 V ± 10%
Rated secondary
output
3 V
Capacity
0.03 VA
For 210 V
Rated primary input
210 V ± 10%
Rated secondary
output
3 V
Capacity
0.03 VA
For 440 V
Rated primary input
440 V ± 10%
Rated secondary
output
3 V
Capacity
0.03 VA
External CT
Rated primary input
5 A
Rated secondary
output
0.1 A
Capacity
5 VA
※
Contact us if the main circuit voltage is not 110 V, 210 V, or 440 V ± 10%.