47
Conversion board model
F408 display
UG-TB4, UG-TB4H
(When no conversion board
is connected)
This function is used to set the optional communication board.
Code
Function name
Setting range
Increment
Unit
Default
value
Changeable
during
operation
F501
Node address
0
to 255
1
–
1
✗
F502
Transmission
rate
[9.6], [19.2], [38.4]
–
kbps
[9.6]
✗
F503
Transmission
mode
[8n1], [8o1], [8E1],
[8n2], [8o2], [8E2]
–
–
[8E1]
✗
F507
Transmission
latency
0
to 999
1
ms
0
✗
These settings may not be required depending on the communication board model, so check
the model before configuring the settings.
Communication board model
Handling of F5 function codes
UG-MBR
The settings can be changed as necessary.
UG-CL
The settings are not required. Use the communication
board with the default values.
* The communication board may fail to operate if the
default values are changed.
F501: Node address
Set the slave address of the unit.
※
Do not to specify an address used by another unit. Doing so may cause incorrect
operation.
※
The Modbus protocol permits decimal values from 0 to 247. Be careful when
specifying other numbers.
※
Address 0 is intended for broadcasting.
F502: Transmission rate
Set the transmission rate of the unit. Set it to match that of the master.