39
Should any display or warning message excluded in the above table be found,please
contact distributor or call EATON Hot line for advice.
ƽ
Indicator light is on
ƾ
Indicator light ashes
Warning include one or more than one of these:
1.EPO active
2.Line loss
3.Neutral loss
4.Line phase error
5.Bypass loss
6.Bypass phase error
7.Battery open
8.Low battery voltage
9.Over charger
10.Battery reverse
11.Charger failure
12.Battery over restrict
ǂ
Low battery voltage
ǂ
ǂ
ƽ
ƾ
One
ashing
every 1 sec
One beep
every 1 sec
ǂ
Overload
ǂ
ǂ
ƽ
ƽ
One
ashing
every 1 sec
One beep
every 1 sec
6
Fault Mode
ǂ
Normal
ǂ
ǂ
ǂ
ǂ
Long light
Long beep
7
Converter Mode
ǂ
Normal
ǂ
ƽ
ƽ
ǂ
None
None
ǂ
Fault
ǂ
ƽ
ƽ
ǂ
One
ashing
every 4 sec
One beep
every 4 sec
8
ECO Mode
ǂ
Normal
ƽ
ǂ
One
ashing
every 1 min
ǂ
None
One beep
every 1 min
ǂ
Fault
ƽ
ǂ
ǂ
ǂ
One
ashing
every 4 sec
One beep
every 4 sec
13.Battery over temperature
14.Fan over restrict
15.BUS capacitor over restrict
16.Fan failure
17.Fan disconnected
18.Low temperature Battery
19.communication disconnected
20.Auxiliary charger failure
21.Bypass N wire cut
22.Battery N wire cut
23.Address conict
Remark:
In fault mode,there is output presented with normal bypass and the bypass LED
will lit(except ECO fault or output short circuit).