11. CONFIGURATION OF THE BATTERY PACK(S)
32
Typical Backup Time of the Battery configuration for reference
1. w/ configuration of 12V24Ah Battery
1 string
2 strings
3 strings
4 strings
5 strings
6 strings
4 kVA
30 min
1 hr
1.7 hr
2.2 hr
3 hr
4 hr
8 kVA
10 min
30 min
45 min
1 hr
1.3 hr
1.7 hr
12 kVA
--
15 min
30 min
40 min
50 min
1 hr
16 kVA
--
10 min
20 min
30 min
40 min
45 min
20 kVA
--
--
15 min
20 min
30 min
40 min
24 kVA
--
--
10 min
15 min
20 min
30 min
2. w/ configuration of 12V38Ah Battery
1 string
2 strings
3 strings
4 strings
5 strings
6 strings
4 kVA
40 min
1.5 hr
2.5 hr
3.5 hr
4.5 hr
6 hr
8 kVA
10 min
40 min
1.2 hr
1.5 hr
2 hr
2.5 hr
12 kVA
--
17 min
40 min
1 hr
1.2 hr
1.5 hr
16 kVA
--
10 min
30 min
40 min
1 hr
1.2 hr
20 kVA
--
--
15 min
30 min
40 min
1 hr
24 kVA
--
--
10 min
17 min
30 min
40 min
3. w/ configuration of 12V65Ah Battery
1 string
2 strings
3 strings
4 strings
5 strings
6 strings
4 kVA
1.5 hr
3.5 hr
5.5 hr
7 hr
9 hr
11 hr
8 kVA
30 min
1.5 hr
2.5 hr
3.5 hr
4.5 hr
5.5 hr
12 kVA
20 min
50 min
1.5 hr
2 hr
2.5 hr
3 hr
16 kVA
10 min
30 min
1.2 hr
1.5 hr
2 hr
2.5 hr
20 kVA
--
25 min
50 min
1.2 hr
1.5 hr
2 hr
24 kVA
--
20 min
30 min
50 min
1.2 hr
1.5 hr
4. w/ configuration of 12V100Ah Battery
1 string
2 strings
3 strings
4 strings
5 strings
6 strings
4 kVA
2.5 hr
5.5 hr
9 hr
12 hr
15 hr
18 hr
8 kVA
1 hr
2.5 hr
4 hr
5.5 hr
7 hr
9 hr
12 kVA
30 min
1.5 hr
2.5 hr
3.5 hr
4.5 hr
5.5 hr
16 kVA
20 min
1 hr
2 hr
2.5 hr
3 hr
4 hr
20 kVA
10 min
40 min
1.5 hr
2 hr
2.5 hr
3 hr
24 kVA
--
30 min
1 hr
1.5 hr
2 hr
2.5 hr