It is easy to operate the equipment, with no previous training. You just need to
read through this manual and operate according to the instructions in it. The
meaning of the LED indicators, please refer to the appendix 1 “Display panel”.

3.1   Operation

1. Turn on the UPS with utility power supplied (in Line mode/AC
mode)

1) After you make sure that the power supply connection is correct,

set the input breaker in the “ON” position first.  At this time the fan
rotates and the UPS supplies power to the load via the bypass.
The UPS operates in Bypass mode.

2) To power on the UPS by simply pressing the “ON” button continu-

ously for more than 1 second.

3) When being powered on, the UPS will perform self-diagnosis,

with the load/battery level LEDs turned on and then off one after
another in ascending order. A few seconds later, the INV LED is
turned on, the UPS is already running in Utility Power mode. If the
utility power is abnormal, the UPS will operate in battery mode
without output interruption of the UPS.

2. Turn on the UPS with no utility power supplied (in Battery mode)

3. Turn off the UPS with utility power supplied (in Line mode/AC
mode)

1) Press the “ON” button continuously for more than 1 second to

power on the UPS. For long back up time model (“S” model),
please make sure that the battery breaker is in “ON” position.

2) During the course of starting up, the UPS has the same action as

if it is connected to utility power except that the utility power LED
is not turned on and the battery LED is turned on instead.

1) Press the “OFF” button continuously for more than 1 second to

turn off the inverter of the UPS immediately.

2) When being powered off, the UPS will perform self-diagnosis,

the Load/Battery level LEDs will be turned on and then off one
after another in ascending order, then the INV LED will be turned
off and Bypass LED will be turned on. The UPS is working in
Bypass mode.

3) Upon completion of the above to turn it off, output of electric

current of the UPS is still present. In order to cut off the output

3. Operation and Operating mode

Summary of Contents for Castle C10K(E)

Page 1: ...Uninterruptible Power Systems CASTLE SERIES C6K e C6KS e C10K e C10KS e USER MANUAL...

Page 2: ...ings and operating instructions in this manual and on the unit strictly Keep this manual properly for fu ture reference Do not operate this unit until reading through all safety information and operat...

Page 3: ...2 2 Input and output power wiring and protective earth installation 2 3 Operating procedure for connecting the long backup time model UPS 3 Operation and operating mode 3 1 Operation 3 2 Operating mo...

Page 4: ...to the following models 1 1 System and model description 1 Brief introduction 1 The C6K e is a standard model with inbuilt battery 2 The C6KS e is a long backup time model which is able to connect wit...

Page 5: ...er Terminal Block Intelligent slot External battery Cable tying BACK VIEW of C6K e C6KS e RS232 Fan Input breaker TB cover Terminal Block Intelligent slot External battery socket Cable tying BACK VIEW...

Page 6: ...ncy Hz 1 Brief introduction 6kVA 4 2kW 6kVA 4 2kW 10kVA 7kW 10kVA 7kW C6K e C6KS e C10K e C10KS e 105 130 load transfers to bypass mode after 10 minutes 130 load transfers to bypass mode after 1 secon...

Page 7: ...ersonnel For safety please cut off the mains power breaker before installation The battery breaker also needs to be cut off if it is a long backup time model S model 1 Open the terminal block cover lo...

Page 8: ...current protective breaker at the output power distribution panel of the UPS if necessary 8 To connect the load with the UPS please turn off all the loads first then perform the connection and finally...

Page 9: ...PS with the external battery Otherwise you may encounter the hazardous of electric shock 1 A DC breaker must be connected between the battery pack and the UPS The capacity of breaker must be not less...

Page 10: ...nnect any loads to the UPS now You should connect the input power wire to the right position first And then set the breaker of the battery pack in the ON position After that set the input breaker in t...

Page 11: ...mal the UPS will operate in battery mode without output interruption of the UPS 2 Turn on the UPS with no utility power supplied in Battery mode 3 Turn off the UPS with utility power supplied in Line...

Page 12: ...power mode The display panel in utility power mode is shown in the following diagram The utility power LED and the INV LED are turned on The load level LEDs will be turnd on in accordance with the loa...

Page 13: ...apacity Note that the load level LEDs in utility power mode will indicate the level of the battery capacity in battery mode instead 1 When the UPS is running in battery mode the buzzer beeps once ever...

Page 14: ...ge or fre quency of the utility power has exceeded the normal range of the UPS 2 Other indications on the display panel are the same in utility mode 3 The UPS does not have the backup function when it...

Page 15: ...battery pack capacity and the load level as well as other factors The backup time of standard model may vary from different models and load level Please refer to the following Discharging Time min Di...

Page 16: ...ty bit None RS232 Interface pin number 3 2 5 Function description Rx Tx Ground I O Input Output Ground Optional AS400 interface This optional AS400 card provides dry contact closure signal OPEN or CLO...

Page 17: ...gions of hot climates the battery should be charged and dis charged every 2 months The standard charging time should be at least 12 hours Under normal conditions the battery life lasts 3 to 5 years In...

Page 18: ...Make sure that there is no voltage before touching the batteries The bat tery circuit is not isolated from the input potential circuit There may be hazardous voltage between the battery terminals and...

Page 19: ...UPS Please contact the distributor or ser vice center Please contact the distributor or ser vice center Turn off the UPS Remove all the loads Ensure that the load is not failed or the UPS has no inter...

Page 20: ...ition Please contact the distributor or ser vice center Check the battery or recharge the battery Press the ON button for more than 1 second Replace the batteries Please contact the distributor to obt...

Page 21: ...hat the loading current is supplied directly from the utility power Utility power LED green LED Whenever the utility power LED is turned on it shows that the utility power is normal INV LED green LED...

Page 22: ...61 80 Battery capacity 41 60 Battery capacity 21 40 Battery capacity 0 20 Battery capacity 96 105 Load capacity 76 95 Load capacity overloaded in utility mode and UPS still in INV mode overloaded in...

Page 23: ...warning 1 2 3 5 6 7 8 9 10 4 Over temperature Continuously beep Inv abnormal Continuously beep Continuously beep BUS voltage abnormal Charger and battery failed 21 25 23 24 20 BAT SCR failed Fan abno...

Page 24: ...ocal laws The Buyer is responsible for certain service and maintenance expenses The following situation is not covered by the warranty finished goods lost or serial number manipulated loss or damage d...

Page 25: ...22 614 06745 00...

Reviews: