User Settings
35
User Settings Guide
No.
Ref. page
Item
Menu
Menu LED
Setting
Setting
LED
Default
Setting
Current
Setting
Remarks
No delay
● ○ ○ ○
*
Linked ON/OFF delay disabled
(operate with delay of 0 seconds)
16 19 3.16
Linked delay
operation
●
○ ○ ○ ○
Delay
○ ● ○ ○
Linked ON/OFF delay enabled
(operate with specified delay)
0 seconds
● ○ ○ ○
*
10 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
5 minutes
○ ● ● ○
10 minutes
● ● ● ○
15 minutes
○ ○ ○ ●
17
20
3.17
Linked operation
ON delay time
●
●○○○
30 minutes
● ○ ○ ●
0 seconds
● ○ ○ ○
*
10 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
5 minutes
○ ● ● ○
10 minutes
● ● ● ○
15 minutes
○ ○ ○ ●
18 21 3.18
Linked operation
OFF delay time
●
○●○○
30 minutes
● ○ ○ ●
Set the ON/OFF delay times when
you conduct linked operation.
Delay operation is not enabled
unless item §3.16 “Enabling and
Disabling Linked Operation Delay”
in the
User Settings Guide is set to
“Delay”.
Set when you connect
a remote switch, or
connect linked
operation cable(s) to
conduct linked
operation.
Disabled
● ○ ○ ○
*
Disable system control
19
22
3.19 Output line control
(Restart)
●
●●○○
Enabled
○ ● ○ ○
Enable system control
0 seconds
● ○ ○ ○
*
5 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
5 minutes
● ○ ● ○
20 23 3.20
Outlet box
OUTPUT1
ON delay time
●
○○●○
10 minutes
○ ● ● ○
0 seconds
● ○ ○ ○
*
6 seconds
○ ● ○ ○
35 seconds
● ● ○ ○
1 minute
30 seconds
○ ○ ● ○
5 minutes
30 seconds
● ○ ● ○
21
24
3.21
Outlet box
OUTPUT2
ON delay time
●
●○●○
10 minutes
30 seconds
○ ● ● ○
Set the ON delay times for the
OUTPUT1 and OUTPUT2 terminals
of the outlet box.
The delay times are not enabled
unless item §3.19 “Enabling and
Disabling Output line Control” in
the
User Settings Guide is set to
“Enabled”.
0 seconds
● ○ ○ ○
*
10 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
22 25 3.22
Outlet box
OUTPUT1
OFF delay time
●
○●●○
5 minutes
○ ● ● ○
0 seconds
● ○ ○ ○
*
10 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
23
26
3.23
Outlet box
OUTPUT2
OFF delay time
●
●●●○
5 minutes
○ ● ● ○
Set the OFF delay times for the
OUTPUT1 and OUTPUT2 terminals
of the outlet box.
The delay times are not enabled
unless item §3.19 “Enabling and
Disabling Output line Control” in
the
User Settings Guide is set to
“Enabled”.
Until batteries
exhausted
● ○ ○ ○
*
0 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
24
27
3.24
Outlet box
OUTPUT1 power
outage output time
●
○○○●
5 minutes
○ ● ● ○
Until batteries
exhausted
● ○ ○ ○
*
0 seconds
○ ● ○ ○
30 seconds
● ● ○ ○
1 minute
○ ○ ● ○
3 minutes
● ○ ● ○
25
28
3.25
Outlet box
OUTPUT2 power
outage output time
●
●○○●
5 minutes
○ ● ● ○
Set the power outage output times
for the OUTPUT1 and OUTPUT2
terminals of the outlet box.
The delay times are not enabled
unless item §3.19 “Enabling and
Disabling Output line Control” in
the
User Settings Guide is set to
“Enabled” and item §3.4 “Setting PC
Interface” in the
User Settings
Guide is set to “Standalone”.
Stop power
supply
● ○ ○ ○
*
26
29
3.26
Operation of Outlet
box OUTPUT0
after stopping of
OUTPUT1 and 2
●
○●○●
Continue
power supply
○ ● ○ ○
Set the operation of OUTPUT0 after
output from the OUTPUT1 and 2
terminals has stopped. This setting
is not enabled unless item§3.19
“Enabling and Disabling Output line
Control” in the
User Settings Guide
is set to “Enabled”.
Set when you connect
an outlet box to perform
output line control.
Output
● ○ ○ ○
*
Output a Ring signal when the UPS starts.
27
30
3.27 Ring signal
●
●●○●
Do not output
○ ● ○ ○
Do not output a Ring signal when the UPS starts.
When you change the setting of the menus indicated by RESTART in the “Menu” column, its changes do not take effect
until you restart the UPS. If a restart is required, be sure to power off the load devices before resetting.
See §11.3 “UPS Shutdown (If Not to Be Used for More Than a Week)” for information about how to shut down the UPS,
and §11.1 “UPS Startup” for information about how to start the UPS.
Note
Summary of Contents for A11H