You can perform tests of the built-in and externally connected batteries. You can do this without stopping
the load devices connected to the UPS.
When it is shipped from the factory, the UPS is set up to perform an automatic battery test once every 6
months. To change the automatic battery test schedule, see §3.14 “Setting Battery Test Schedule” in the
User Settings Guide
.
Follow the procedure below when conducting a manual battery test. However, if the UPS has performed a
backup operation within 24 hours (A11H***011) or 36 hours (A11H***111) prior to the test, the result may
show an error. The test should, therefore, be conducted when the UPS has not performed a backup
operation within the last 24 or 36 hours.
The “Green BATT. TEST” indicator starts blinking, and the battery test starts.
The test finishes
in about 90 seconds.
Check the “Green BATT. TEST” indicator for the results of the test.
Green BATT. TEST
lit
blink
Buzzer
-
******* 7 beeps ... ******* 7 beeps ....
Confirmed
Backup Time
90 seconds
or more
Less than 90 seconds
Result
The batteries
are OK.
Replacing the battery early is recommended.
Contact SANYO DENKI.
The “Green BATT. TEST” indicator goes off and returns to its normal indication.
Hold for 2 seconds.
①
Press
and hold it for at least 2 seconds.
②
After the battery test has finished and the “Green BATT. TEST” indicator lights
or blinking, press
.
The results of the test are only an approximate guide. If the batteries have reached their replacement
interval, an early replacement is recommended even if the results of the test are OK. See “Estimated
battery replacement interval” in the previous page for more information.
To stop the battery test while it is underway,
Press
for at least 2 seconds
⇒
The UPS returns to normal operation.
The battery test stops if any of the following 1-3 occur or if any of the following 4-7 is operated while
it is underway.
The “Green BATT.TEST” indicator does not display the results of the test if the test is interrupted.
Stopping battery test
1. Input power error (voltage or frequency).
2. Mechanical failure
3. Output power overload
4. Switching of Forced Bypass switch
5. Setting MAIN MCCB to “OFF”
6. Pressing
for 1 second or longer
7. Executing the battery test stop by the power
control software
Battery Test Results
Note
Buzzer
2 beeps... 2 beeps... 2 beeps...
LED
Green BATT. TEST Blinking
Battery operation for about
90 seconds