Instruction Manual for SABER PRO WIRELESS 24V
1-888-726-8869
www.sanuvox.com
3. The
main bracket can be mounted to the side of the duct allowing the
UV lamp to be inserted in-between or over the A coil.
Drill a 1" diameter hole in the sheet metal to allow the UV lamp to pass,
and mount the main bracket to the side of the duct using the 2 included
sheet metal screws. Once installed, use the round metal washer to lock
the lamp in place. Then tighten the 2 screws with care.
4. Plug the connector onto the lamp pins.
The plug is designed so that
it can only be installed one way. You may have to rotate the socket 90°
to line up the pins with the holes.
STEP 3
STEP 4
STEP 5
STEP 6
5. Drill a 0.25" hole on the outside of the plenum and install the view port.
When the lamp is ON, the glow of the lamp will be visible through this port.
6. Connect the two black wires to the 24 VAC terminals on the HVAC
equipment.
NOTE:
Make sure that the HVAC equipment can at least supply 20 VA.
If not, we recommend the use of a dedicated transformer that provides
24 VAC with a minimum of 20 VA, otherwise it will not be sufficient to power
the ballast and lamp. An alternative is to use a step down transformer
24 to 27 VA on a 120V plug.
STEP 7
7. And finally, reconnect power to the HVAC unit or system, or plug in the
transformer in a power outlet.