Input plug shape
■
Output outlet shape
NEMA L5-30P
NEMA 5-15R
NEMA L5-30R
Output capacity
3
kVA
Terminal block type in the next page
Free-standing type
Order no.
(A set of a UPS unit and battery units)
S-A11KL302B0250TSN00
S-A11KL302B0300TSN00
Rack mount type
Order no.
(A set of a UPS unit and battery units)
–
–
Rated output capacity
(apparent power / active power)
3 kVA / 2.4 kW
Battery backup time
(2)
250 min
300 min
Battery capacity [Ah·cell]
5520
6624
Battery power consumption [Wh]
12420
14904
Input plug
NEMA L5-30P
Output outlet
NEMA L5-30R × 1, NEMA 5-15R × 2 (15 A each)
Acoustic
noise
During normal operation
46 dB or less
During battery operation or at a
temperature above 40
°
C
55 dB or less
Heat dissipation (At rated operation,
after battery charging completed)
254 W
Input leakage current
3.5 mA or less
Operating environment
Ambient temperature: -20 to +55
°
C,
(2)
humidity: 10 to 90% RH (non-condensing)
Free-standing type - Dimensions
(3)
(Unit: mm)
Drawing
Fig. 7
Fig. 8
W
435
435 + 435 (+ 65)
H
1111
761
D
520
520
Mass
294 kg
192 + 170 kg
Rack mount type - UPS unit dimensions
(3)
(Unit: mm)
Drawing
―
W
―
H1
―
D
―
Mass
―
Rack mount type - Battery unit dimensions
(3)
(Unit: mm)
Drawing
―
W
―
H2
―
D
―
Mass
―
(1) At 25
°
C ambient temperature and load power factor of 0.8, using new, fully charged batteries.
(2) Battery charging will stop when battery temperature exceeds 55˚C.
(3) Dimensions do not include protruding objects like screws.
H
17
5
17
5
17
5
W
(8)
D
13
1
17
5
1
7
5
Joining brackets (Supplied)
W
(80)
25
Fig. 7
Joining brackets (Supplied)
W
17
5
1
3
1
17
5
17
5
W
(8)
D
17
5
630
17
5
17
5
520
H
25
25
(80)
(80)
(65)
Fig. 8
17
CATALOG No.P1023B006 ‘21.6
SANUPS
A11K-Li