5. USING THE UPS (APPLICATION)
_
30
Step
Description
Remarks
2
2
Prepare the switch in accordance with the system.
The remote switch is provided as an option as well.
For option details, contact your sales representative or
SANYO DENKI.
3
3
If the UPS is running, stop the UPS by performing the procedure in “4.2.2
Shutting Down the UPS”.
Unplug the UPS input plug from the outlet or turn the
outlet breaker OFF, and shut down the UPS. Failure to
completely shut down the UPS may result in electrical
shock.
4
4
Connect the prepared switch prepared to REMOTE terminals 1 to 4.
4-1 Strip roughly 9 to 10 mm of insulation from the end of the wire.
4-2 Insert the wire into the terminals 1 to 4 while pressing the tab with an
insulated flat-head screwdriver.
4-3 Pull the wire to check it does not come out.
The terminals of EPO 5 and 6 are for connecting the
emergency stop switch.
Be careful not to mix up the connecting terminals.
5
5
Press the ON/OFF button of the remote switch to verify UPS operation.
Hold down the ON/OFF button of the remote switch for
at least one second.
6
6
Run the UPS in accordance with the system.
Check operation before actual use.
Remote switch
Hold down the button for
at least 1 second.
Terminal Nos. 1 to 4
Insert and remove the
wire while pressing the
tab with an insulated
flat-head screwdriver.
1 2 3 4 5 6
REMOTE
□ □
ON OFF
REMOTE
ON OFF
When the conduction part is
short, a reliable connection
cannot be made.
9〜
10m
m