Fig. F1-6 Hopping Frequency
F1.31
Action when set freq. is lower than lower limit freq.
0
~
2
0
0
:
run at lower limit frequency
VFD runs at lower limit frequency when set frequency is lower than lower limit frequency setting value (F0.17).
1
:
run at zero frequency after delay time
When set frequency is lower than lower limit (F0.17), after delay time (F1.32), the VFD will run at zero frequency.
2
:
stop running after delay time
When set frequency is lower than lower limit (F0.17), after delay time (F1.32), the VFD will stop running.
F1.32
Delay time of stopping when frequency is lower than
lower limit
0.0
~
3600.0s
10.0
For details check F1.31 parameter description.