242
Read parameter value +
attribute value + min.value
of F0.12
Send frame
:
01H 13H 000CH 0003H 040BH
Return frame
:
01H 13H 06H 1388H 0322H 0000H 628BH
Read parameter value +
min.value + max.value of
F0.12
Send frame
:
01H 13H 000CH 0004H 45CBH
Return frame
:
01H 13H 08H 1388H 0322H 0000H 1388H 2831H
5.3 Functions of other Register Address:
function
address
description
VFD operation
status
A000H(1A00H)
byte
bit
meaning
Byte1
Bit7
0: no action
1: overload pre-alarm
Bit6
~
Bit5
0:INV_220V
1:INV_380V
2:INV_660V
3:INV_1140V
Bit4
0: no action
1: power off save