54
F5.18
controller adjustment
cycle of voltage closed
loop output
0.01
~
10.00s
0.01s
0.10
×
F5.19
Voltage rising time
0.1
~
3600.0s
note
:
this parameter is only
valid for open loop output
mode of complete separated
voltage
0.1s
10.0
○
F5.20
Voltage declining time
0.1s
10.0
○
F5.21
Voltage
feedback
disconnection
treatment
0
:
alarm and keep running with
the voltage of disconnection
moment
1
:
alarm and keep running with
decreased voltage of amplitude
limiting value
2
:
protection action and free
stop
1
0
×
F5.22
Detection
value
of
voltage
feedback
disconnection
0.0
~
100.0%*rated voltage of
motor
0.1%
2.0%
○
F5.23
Detection
time
of
voltage
feedback
disconnection
0.0
~
100.0s
0.1s
10.0
○
F5.24
Limit voltage of voltage
feedback
disconnection
0.0
~
100.0
%
*rated voltage of
motor
note
:
this voltage represents
the output voltage of VFD, and
reasonable setting of this
0.1%
80.0%
○