80
(
electronic heat relay, without
low speed compensation
)
FA.01
Motor
overload
protection factor
20.0
%~
120.0
%
0.1%
100.0%
×
FA.02
Undervoltage
protection
0
:
disabled
1
:
enabled
(
undervoltage is seen
as fault
)
1
0
×
FA.03
Undervoltage
protection level
220V
:
180
~
280V 200V
380V
:
330
~
480V 350V
1V
Depending
on model
×
FA.04
Overvoltage limit level
220V
:
350
~
390V 370V
380V
:
600
~
780V 660V
1V
Depending
on model
×
FA.05
Voltage limit factor in
decelerating
0
~
100
0
:
protection invalid of stall over
voltage
1
Depending
on model
×
FA.06
Current
limiting
threshold (only valid
for VF mode)
G type
:
80
%~
200
%
*VFD rated
current 160%
P type
:
80
%~
200
%
*VFD rated
current 120%
1%
Depending
on model
×
FA.07
Current limiting in the
field weakening region
0
:
limited by FA.06
1
:
limited by conversion value of
PA.06
1
0
×
FA.08
Current limiting factor
in accelerating
0
~
100
0
:
acceleration current limiting
is disabled
1
Depending
on model
×