User Manual & Datasheet V 2.1
15
Menu and Description
For Menu please refer Table 5 and 6
MENU
SUB MENU
CHANGE
DESCRIPTION
REMARK
rLdr (Relay Drive)
r. FS
FS. H <>FS. L
Fail Safe Selection
FS.H/ FS.L:Fail Safe
High/Low
rLdr (Relay Drive)
r.oPt
o.Ind<>o.PUM
Control Action Selection
Ind : Individual, PUM :
Pump
rLdr (Relay Drive)
r. SP
S.000<>S.100
Set point Only in Indi-
vidual Controlling
rLdr (Relay Drive)
r.SPH
h.001<>h.100
Higher Set point Only in
Pump Controlling
SPH must be higher
than SPL
rLdr (Relay Drive)
r.SPL
L.000 <>L.099
Lower Set point Only in
Pump Controlling
SPH must be higher
than SPL
rLdr (Relay Drive)
r.Cd
C.000 <>C.100
Cover Delay in Seconds
rLdr (Relay Drive)
r.Ud
U.000 <>U.100
Uncover Delay in Sec-
onds
SCAL (Scal Factor)
SC.-H
H.020<>H.100
Higher SCALE LEVEL
SCAL-HIGH must be
20% or more Higher
than SCAL-LOW
SCAL (Scal Factor)
SC.-L
L.000<>L.080
Lower SCALE LEVEL
SCAL-HIGH must be
20% or more Higher
than SCAL-LOW
dISP(Display)
d.PER<>d.AmP
Display Options PER
: Percentage, AmP :
mAmp
Table 5: Menu
Sapcon Instruments Pvt.Ltd.
R