Chapter 5 Setting Up the ETC II
Configuring Data Server
ETC II Network Communicator
45
Logging interval: 1 (in polling interval
units)
New:
Data Server Exchanges
See
Data Server
in Chapter 3 for more information on using Data server
exchanges.
To inspect the present configuration (to leave the settings unchanged, just
press Enter) or configure the Data server exchanges:
1.
Type
s
and press Enter. The following prompt appears:
Data server>s
Data Exchange No:
2.
Type the data exchange number, and then specify the device address,
the start device register and the number of registers in the real-time
data exchange. Note that the real-time, status event and write data
exchanges with the same exchange number are internally linked in the
ETC II to the same device address.
Device ID: 1
New:
Start device register address: 256
New:
Number of registers: 1
New:
3.
Enable real-time polling for the exchange if you want to start exchange
operations:
Polling: enabled
New [y/n]:
4.
Enable updating the real-time clock in the device if you wish to
periodically synchronize its clock with the ETC II clock:
RTC update: disabled
New [y/n]:
5.
Specify the start device register and the number of registers in the write
data exchange:
Write block start register address: 200
New:
Number of registers: 10
New:
6.
Enable polling for the write data exchange if you want to start exchange
operations:
Polling: disabled
New [y/n]:
7.
Specify the device status register and a register mask for a status event
exchange:
Status register address: 400
New:
Status register mask: 0xC000(HEX)
New:
8.
Enable polling for the status event exchange if you want to start
exchange operations:
Status polling: disabled
New [y/n]: