Chapter 5 Setting Up the ETC II
Configuring Data Server
ETC II Network Communicator
47
See
Data Server
in Chapter 3 for more information on using real-time data
exchanges. Refer to the ETC II Modbus Guide for information on how to
access the acquired real-time and logged data via communications.
The following table lists available options.
Parameter
Options
Default
Description
Device Address
1-247
1
Defines the device to which
the exchange is linked
Device Start Register
0-65535
0
Defines the start device
register
for
real-time
polling
Block Size
1-114
0
Defines the number of
contiguous registers in the
exchange
Polling Enabled
Disabled,
Enabled
Disabled
Enables polling the device
RTC Sync Enabled
Disabled,
Enabled
Disabled
If enabled, the Data server
synchronizes the device
clock with the ETC II clock
To configure a real-time data exchange:
1.
Define the device address for a data exchange. Note that the real-time,
status event and write data exchanges with the same exchange number
are internally linked in the ETC II to the same device address.
2.
Specify the start register address of the area in the device Modbus map
you wish to be polled via the exchange.
3.
Type the number of registers in the exchange. Up to 114 registers can
be specified for a single exchange. As you type the register address
range, PAS immediately shows you the start register address in the
ETC II exchange area for accessing the acquired data from the remote
applications.
4.
Check the “Polling Enabled” box to activate the exchange.
Status Event Exchanges
To enter the Setup dialog, select the ETC II site from the list box on the PAS
toolbar, select ETC II Setup from the Meter Setup menu, and then click on
the Status Event Exchanges tab.