Chapter 5 Setting Up the ETC II
Configuring Data Server
ETC II Network Communicator
49
See
Data Server
in Chapter 3 for more information on using data exchanges.
Refer to the ETC II Modbus Guide for information on how to put data into a
write exchange and to trigger it via communications.
The following table lists available options.
Parameter
Options
Default
Description
Device address
1-247
1
Define the device to which
the exchange is linked
Device Start Register
0-65535
0
Defines the start device
register for a write
Block Size
1-12
0
Defines the number of
contiguous registers in the
write exchange
Write Enabled
Disabled,
Enabled
Disabled
Enables writing data to the
device upon a trigger
To configure a write data exchange:
1.
Define the device address for a write data exchange. Note that the real-
time, status event and write data exchanges with the same exchange
number are internally linked in the ETC II to the same device address.
2.
Specify the start register address of the area in the device Modbus map
you wish to be written via the exchange.
3.
Type the number of contiguous registers in the exchange.
4.