background image

SATEL CA-64E 

 
 

 
 

 
 

 

 
 

Fig. 3. Example of DIP switch settings. 

 

2.  Mounting and installation 

Caution: Prior to starting the module hookup, switch off power supply of the security 

system. 

1.  Fasten the expander board in its housing. 

2.  Using cables, connect the terminals CLK, DTA and COM to the expander bus on 

the control panel main board. 

3.  Using the DIP switches, set up the appropriate expander address and the type of 

the supported detectors. 

4.  Connect the detector leads (for connection description refer to the alarm control 

panel installer manual). 

5. Connect the leads of the tamper contact on expander housing to the terminals 

TMP and COM. Where two expanders are installed in the housing, the TMP input 
of one expander is to be shorted to ground, and the contact leads are to be 
connected to the TMP input of the other expander. 

6.  Connect the power supply leads to the ter12V and COM. The expander 

supply voltage need not be provided from the control panel main board. A power 
supply unit or another expander with power supply can be used for this purpose. 

3.  Starting the expander 

1.  Turn on power supply of the security system. The LED indicating communication 

with the alarm control panel will come on with steady light. 

2. Call the "Expander identification" function in the LCD keypad  (

Æ

Service mode 

Æ

Structure 

Æ

Hardware 

Æ

Identification). When the identification is completed, the 

LED which indicates communication with the alarm control panel will start blinking. 

Note: In the process of identification, the control panel writes to the module memory 

a special (16-bit) number intended to detect the module presence in the system. 
Replacement of the expander with another (even one having the same address 
set up on the switches) without a new identification will trigger alarm (module 
tamper – verification error). 

3.  Using the LCD keypad or computer (

D

LOAD

64

 or 

D

LOAD

X

 program, depending on 

the control panel type), perform programming of the module zones. 

4.  Save the module settings in the control panel memory. 

address: 

22 

type of supported zones: 

NO, NC, EOL, 2EOL/NO, 

2EOL/NC, vibration and roller 

(setting for INTEGRA panels 

with firmware in version 1.05 or 

later) 

Summary of Contents for CA-64 E

Page 1: ...LK DAT 12V 12V ADRES 12345 STATUS 1 2 Fig 1 Schematic view of the expander electronics board Legend 1 LED SATUS to indicate the process of communication between control panel and expander blinking data exchange with the panel ON no data exchange with the panel the module and the control panel connecting wire is damaged identification of module is not carried out or the STARTER program is started i...

Page 2: ...d to one bus This will permit problems to be avoided during extension of the alarm system To determine the type of detectors to be supported and the method of expander identification in the system use the switch 8 If the switch is set to OFF position the expander zones can be programmed as NO NC EOL 2EOL NO or 2EOL NC If the switch 8 is set to ON position the expander zones can be programmed as NO...

Page 3: ...er supply unit or another expander with power supply can be used for this purpose 3 Starting the expander 1 Turn on power supply of the security system The LED indicating communication with the alarm control panel will come on with steady light 2 Call the Expander identification function in the LCD keypad ÆService mode ÆStructure ÆHardware ÆIdentification When the identification is completed the L...

Page 4: ...nstalled may cause considerable changes in the system If such a situation occurs you can restore the previous status by means of the DLOADX program INTEGRA series or the DLOAD64 program CA 64 control panel Open the Hardware tab in the Structure window and click on the expander in which you want to change the zones numeration and then click on the Advanced settings button in the right hand lower co...

Reviews: