INT-SCR-BL SATEL
7
6. Operation in the Mode of Partition Keypad with Proximity Card
Reader
Information conveyed by the keypad with LED indicators in this mode is identical to that in the
partition keypad mode. Additionally, all LEDs of the partition keypad with reader blinking
simultaneously indicate waiting for the card read-in (during the procedure of adding a card to
the user).
Information on the use of the partition keypad with proximity card reader can be found in the user
manual of the control panels.
The partition keypad with proximity card reader can be programmed by means of the LCD keypad
(
S
ERVICE MODE
S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
expander selection
)
or a computer with the
D
LOAD
X
program. The operating mode of partition keypad with proximity card
reader offers all the functions available for the partition keypad mode. Support of the proximity cards
should only be additionally taken into account. Presenting the card to the reader is recognized by the
expander as entering the code, confirmed with the key. Holding up the card for approx. 3 sec. is
recognized as entering the code, confirmed with the
key.
7. Operation in the Entry Keypad Mode
In the entry keypad, only the LED designated
is used for signaling. Blinking of the LED informs
that the countdown of delay activation time is running (disarming has no effect on the LED blinking).
Information on the use of the entry keypad can be found in the user manual of the control panels.
The entry keypad can be programmed by means of the LCD keypad (
S
ERVICE MODE
S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
expander selection
) or a computer with
the
D
LOAD
X
program. Described below are settings and options available for programming.
Name
– option to give an individual (16-character) name to the module. This option can be accessed
in the LCD keypad as follows:
S
ERVICE MODE
S
TRUCTURE
H
ARDWARE
E
XPANDERS
N
AMES
expander selection
.
Partition
– assignment of the keypad to a partition selected from the list. The delay activation will
apply to the zones with reaction type
3. I
NTERIOR DELAYED
in this partition.
Master users/Users
– this function defines master users/users authorized to use the given keypad.
Alarm 3 incorrect codes
– entering a wrong code or reading in an unknown card three times will
trigger alarm.
Control BI
output
– the keypad can handle codes of the
B
ISTABLE OUTPUTS
type (control of the type
25. BI
SWITCH
outputs).
Control MONO
output
– the keypad can handle codes of the
MONO
OUTPUTS
type (activation of the
type
24. MONO
SWITCH
outputs).
Guard round control
– entering the guard code ended with
or
key as well as presenting or
holding up the card will be recorded as completion of the round.
Signaling
Delay activation sign.
– the keypad is acoustically signaling the countdown of delay unblocking
time.
Access code signaling (hardware)
– the keypad itself, independently of the control panel, will
audibly acknowledge entering the access code. This signaling is useful if there is a delay
between the code entry and the audible information generated after verification of the code by
the control panel.
Confirming
– this option defines the way of communication between the control panel and the
keypad user:
No
– the module provides no information on execution of or refusal to execute an operation.
Sound
– the module provides information on execution of or refusal to execute an operation by
means of beeps (see: control panel user manual).