SATEL
INT-SK
5
Lock features
[Lock function] – mode of operation of the relay output after the access is
granted:
ON if partition armed
[On if part.armed] – the relay output will be turned on until the
partition is armed. When the partition is armed, users cannot get access (to get access,
the user must disarm the partition).
Fixed ON time
[ON time] – the relay output will be turned on for the “Relay ON time”.
Fixed ON time – OFF if door open
[ON, open
off] – the relay output will be turned on
until the door is opened (door status input is disconnected from common ground),
however not longer than for the “Relay ON time”.
Fixed ON time – OFF if door closed
[ON, close
off] – the relay output will be turned on
until the door is closed (door status input is reconnected to common ground), however
not longer than for the “Relay ON time”.
Relay ON time
– the time during which the relay output can be turned on after the access is
granted. You can program from 1 to 255 seconds. The parameter does not apply to the
“ON if partition armed” mode.
Fig. 4. DLOADX program: parameters and options of partition keypad.
Relay
[Relay type] – status of the deactivated relay:
NO
[Normal.open NO] – the relay contacts are open (they close on activating the relay).