background image

SATEL 

INTEGRA 128-WRL 

21 

system should be instructed on how to disconnect the transformer from the mains (e.g. by 
indicating the fuse which protects the control panel supply circuit). 

5.9.2  Backup power supply 

A 12 V lead-acid sealed battery should be connected to the control panel as a backup power 
source. The battery capacity must be adequately selected to match current consumption in 
the system. According to EN 50131 Grade 2, the battery must ensure operation of the system 
without mains supply for 12 hours. 

Do not connect deeply discharged battery to the control panel (with voltage 
across unloaded terminals below 11 V). The battery should be precharged with 
a proper charger. 

The used batteries must not be discarded, but should be disposed of in 
accordance with the existing rules for environment protection. 

If the battery voltage drops below 11 V for longer than 12 minutes (3 battery tests), the 
control panel will indicate battery failure. When the voltage goes down to approx. 10.5 V, the 
battery will be disconnected. 

5.9.3  Control panel power-up / start-up procedure 

1.  Deenergize the 230 V AC circuit to which the transformer is to be connected. 

2.  Connect the 230 V AC wires to the terminals of transformer primary winding. 

3.  Connect the terminals of transformer secondary winding to the AC terminals on control 

panel electronics board. 

4.  Connect the battery to the dedicated leads (positive terminal to RED lead, negative 

terminal to BLACK lead). 

The control panel will not start after connecting the battery 

alone. 

Included in the control panel set are adapters (matching connectors) for 

connection of battery with twisted cable ends, therefore the battery cable ends should not 
be cut off. 

5.  Turn on 230 V AC power supply in the circuit to which the transformer is connected. 

The control panel will start operating. 

If you have any problems with starting the control panel, enter the service mode 
“from the pins”  and restore the factory default settings (see E

MERGENCY 

PROCEDURE OF THE CONTROL PANEL START

-

UP

 p. 22). 

The above mentioned power-up sequence (first the battery, then the 230 V AC mains) will 
ensure proper operation of the power supply unit and the electronic protection circuits, thus 
preventing damage to the alarm system components caused by installation mistakes, if any. 

If the control panel power supply has to be disconnected, disconnect the mains first 
and then the battery. When reconnecting the power supply, observe the above 
mentioned sequence. 

5.10  First start-up of the control panel 

After the first start-up of the control panel, it is advisable to restore the factory 
default settings using the C

LEAR ALL

  function ([S

ERVICE CODE

]

 

S

ERVICE MODE

 

R

ESTARTS

 

C

LEAR ALL

), and then quit the service mode. When a prompt 

appears on the keypad display, whether the data should be saved to the FLASH 
memory, press the “1” key on the keypad. 

Summary of Contents for Integra 128-WRL

Page 1: ...INSTALLER MANUAL SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu integra wrl_i_en 08 21 Alarm Control Panels INTEGRA 128 WRLFirmware version 1 20...

Page 2: ...under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being...

Page 3: ...ware version 1 20 Keypads Support for new keypads INT TSG2 and INT TSH2 Outputs New option AC LOSS FAST for the 28 AC LOSS MAINBOARD IMMEDIATE type outputs Reporting New option for the SIA IP format E...

Page 4: ...essing devices connected to the expander bus 18 5 7 Connecting the detectors 18 5 7 1 End of line resistors 19 5 8 Connecting the sirens 20 5 9 Connecting power supply 20 5 9 1 Main power supply 20 5...

Page 5: ...of end of line resistors several dozen zone types Maximum number of programmable zones 128 Outputs 8 programmable hardwired outputs on the control panel mainboard 2 high current outputs 6 low current...

Page 6: ...ging to 16 phone numbers in the form of 16 voice messages played back by an additional module INT VG CA 64 SM or SM 2 64 text messages defined by the installer PAGER or SMS Event log 21503 events A se...

Page 7: ...modem serial printer connection for printing current events Capability of the firmware updating without the need for disassembly of the control panel Socket for connecting the INT VG voice module CA...

Page 8: ...he status of the partitions and the system Backlit keys Built in sounder 2 programmable hardwired zones support for NO and NC detectors support for Single EOL and Double EOL configuration Tamper prote...

Page 9: ...keypad It allows the user to activate delay for the 3 INTERIOR DELAYED type zones After expiry of the time period preset on the keypad unless the system is disarmed the interior delayed zones will ag...

Page 10: ...8 Installer Manual SATEL Fig 1 INTEGRA 128 WRL security alarm system...

Page 11: ...motion detector APD 100 wireless passive infrared detector APMD 150 wireless dual motion detector ARD 100 wireless reorientation detector ASD 110 wireless smoke and heat detector ASD 150 wireless smo...

Page 12: ...2 5 mm Phillips screwdriver precision pliers flat nose pliers driller c w a set of drill bits 5 1 Installation plan The installation must be preceded by preparation of a plan of the security alarm sy...

Page 13: ...device should not exceed 1 V as against the output voltage In order to guarantee correct functioning of the system components it is important that resistance and capacitance of the signal wires be as...

Page 14: ...ns for Fig 2 battery connection cables red black LEDs indicating the status of high current outputs pins for setting battery charging current pins shorted jumper on 400 mA pins open no jumper 800 mA C...

Page 15: ...SATEL INTEGRA 128 WRL 13 Fig 2 Control panel mainboard version 2 1...

Page 16: ...dicating the status of low current outputs socket for connecting the INT VG voice module INT AV audio alarm verification module CA 64 SM voice synthesizer expander or SM 2 synthesizer socket for GSM G...

Page 17: ...to set correct individual addresses in the keypads and perform identification of all devices connected to the bus In other devices to be connected to the keypad bus the address is to be set using the...

Page 18: ...keypad CKM and DTM terminals 8 Connect the keypad correctly to the control panel 5 5 2 Numeration of keypad zones The address set in the keypad defines which numbers in the system will be assigned to...

Page 19: ...with GUARDX program is connected Data exchange with the computer will begin automatically as soon as the GUARDX program is started 5 6 Connecting devices to the expander bus Fig 6 Connection of module...

Page 20: ...e connected to the dedicated socket on the control panel electronics board 5 6 2 Addressing devices connected to the expander bus Each device to be connected to the expander bus must have its own indi...

Page 21: ...zone will also accept connection of a detector with the NC alarm output e g a shock detector and a magnetic contact can be connected in series Follow output in case of this configuration the detector...

Page 22: ...e battery Before connecting power supply insert the clock and RAM backup battery into its socket on the mainboard 5 9 1 Main power supply The control panel requires 18 V AC 10 power supply Using a tra...

Page 23: ...panel electronics board 4 Connect the battery to the dedicated leads positive terminal to RED lead negative terminal to BLACK lead The control panel will not start after connecting the battery alone I...

Page 24: ...e identified device with another one having the same address will trigger a tamper alarm 5 11 Emergency procedure of the control panel start up If the control panel fails to start properly keypads are...

Page 25: ...ansmit data over the cellular network it is recommended that you use SIM cards with a dedicated tariff plan for M2M machine to machine communication Having started the control panel you can start up t...

Page 26: ...re wireless devices The number of positions on the list is at the same time the number of zones and in case of some devices also outputs which will be taken by the device in the system When adding and...

Page 27: ...d unavailable 5 AMD 100 detector 21 AMD 100 detector 21 unused unavailable 6 AMD 100 detector 22 AMD 100 detector 22 unused unavailable 7 AMD 101 detector 23 AMD 101 detector 23 unused unavailable 8 2...

Page 28: ...battery into the device turn on the device power etc 5 Type and serial number of the device will be displayed if a message is displayed instead to inform you that the entered serial number is invalid...

Page 29: ...s will be displayed 3 Use the and keys to select the zone to which the device you want to remove is assigned 4 Press 5 Press the key 1 to confirm that you want to remove the device pressing another ke...

Page 30: ...el computer with DLOADX program required or remote administration of the security alarm system computer with GUARDX program required The communication is encrypted The control panel can work with any...

Page 31: ...arameters to be programmed see example in Fig 14 The parameter block saved as the profile 0 in Fig 14 STORED PROFILE 0 should include E1 Q0 V1 X4 D2 S0 and S00 000 In such a case the modem is ready fo...

Page 32: ...ne containing up to 80 characters or extended format with names of zones partitions users and modules then the event is printed in two lines when the printer with up to 80 characters per line is used...

Page 33: ...d The same rules apply to the wireless outputs the numbers of keypad zones are determined during the identification procedure based on the keypad address see section NUMERATION OF KEYPAD ZONES p 16 th...

Page 34: ...event log user data clock settings will be lost 8 Specifications 8 1 Control panel Supply voltage 18 V AC 15 50 60 Hz Recommended transformer 40 VA Standby current consumption from AC mains 120 mA Ma...

Page 35: ...106 mm Enclosure dimensions OPU 3P 324 x 382 x 108 mm Weight incl enclosure and accessories 2130 g 8 2 INT KLCD keypad Supply voltage 12 V DC 15 Standby current consumption 17 mA Maximum current cons...

Page 36: ...on 110 mA Environmental class according to EN50130 5 II Operating temperature range 10 55 C Maximum humidity 93 3 Enclosure dimensions 160 x 132 x 29 mm Weight 317 g 8 7 INT KLFR keypad Supply voltage...

Page 37: ...d s 5 2016 04 1 15 Information on AOD 200 detector has been added p 9 and 26 Note on checking the battery status has been added p 12 2017 05 1 17 Information on AOCD 250 detector has been added p 9 In...

Reviews: