background image

®

 

IVORY 

PASSIVE INFRARED DETECTOR 
WITH MIRROR OPTICS 

ivory_en 01/15 

The IVORY detector allows detection of motion in the protected area. This manual applies to the 
detector with electronics version 2.3 or newer. 

1.  Features 

  High-quality segmented mirror. 

  Advanced digital signal processing. 

  Digital temperature compensation. 

  Adjustable detection sensitivity. 

  Built-in EOL resistors. 

  LED to indicate alarm status. 

  Remote LED enable/disable. 

  Alarm memory. 

  Supervision of detector signal path and supply voltage. 

  Tamper protection against cover removal. 

2.  Description 

After motion is sensed by the detector in the coverage area, the alarm relay contacts will open for 
2 seconds. 

Supervision features 

In the event of the voltage drop below 9 V (± 5%) for more than 2 seconds or the signal path 
failure, the detector will signal a trouble. The trouble is indicated by the activation of alarm relay 
and the steady red light of LED indicator. The trouble signaling will continue as long as the 
trouble persists. 

Remote LED enable/disable 

The  LED can be enabled/disabled remotely when the jumper is placed across the LED pins in 
OFF position. The LED terminal is provided to allow remote LED enable/disable. The LED is 
enabled, when the terminal is connected to the common ground, and disabled, when the terminal 
is disconnected from the common ground. You can connect to the LED terminal an OC type 
control panel output programmed e.g. as the 

S

ERVICE MODE STATUS

BI

  SWITCH 

or 

Z

ONE TEST 

STATUS

Alarm memory 

If the LED is enabled, the detector can signal the alarm memory. The MEM terminal is provided 
to allow the alarm memory enable/disable. The alarm memory is enabled, when the terminal is 
connected to the common ground. The alarm memory is disabled, when the terminal is 
disconnected from the common ground. If the alarm memory is enabled and an alarm occurs, the 
LED will start blinking. Indication of the alarm memory will continue until the alarm memory is 
enabled again (the MEM terminal is connected to the common ground). Disabling the alarm 
memory will not stop the alarm memory indication. You can connect to the MEM terminal an OC 
type control panel output programmed e.g. as the

 

A

RMED STATUS