4.2  Maximum output loads for lighting 

Incandescent lamps ....................................................................................................... 3680 W 

HV 230V halogen lamps ................................................................................................ 3680 W 

LV halogen lamps: 

 

inductive transformer ....................................................................................... 2000 VA 

 

electronic transformer ........................................................................................ 2500 W 

Fluorescent lamps: 

 

non compensated .............................................................................................. 3680 W 

 

parallel compensated .......................................................................... 2500 W, 200 

µF 

 

series compensated ............................................................................ 3680 W, 200 

µF 

Compact fluorescent lamp (CFL): 

 

non compensated .............................................................................................. 3680 W 

 

parallel compensated .......................................................................... 2500 W, 200 

µF 

High-pressure mercury lamps: 

 

non compensated .............................................................................................. 3680 W 

 

parallel compensated .......................................................................... 3680 W, 200 

µF 

Exceeding  the  limit  values  of  the  module  working  parameters  may  damage  the 
module and pose hazard to human health or life. 

 

Summary of Contents for KNX-SA41

Page 1: ...iversal Switch Actuator Quick installation guide Full manual is available on www satel eu Firmware version 1 01 knx sa_sii_en 11 19 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320...

Page 2: ...hts under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes be...

Page 3: ...D is assigned to each channel ON channel enabled OFF channel disabled buttons to manually change the channel state One ON OFF button is assigned to each channel The manual change of channel state is m...

Page 4: ...umber of circuits and relays in the module is contained in the module symbols KNX SA41 KNX SA24 The first digit in the symbol means the number of circuits in the module and the second the number of re...

Page 5: ...Connect the loads to load circuit terminals 4 Connect module power to N and L terminals All connections should be made in accordance with the wiring diagram for the given module see Wiring diagram 5 C...

Page 6: ...rol buttons grouped in the upper row of buttons A C E G to reset memory The indicator LEDs situated above the buttons will go on 5 Hold down the buttons until the indicator LEDs go off about 10 second...

Page 7: ...tive AC1 600 cycles hour 105 16 A 250 VAC resistive DC1 600 cycles hour 105 16 A 24 VDC AC3 I 3 5 A 2 5 x 105 at incandescent lamp load 1000 W 0 9 x 105 Connections Maximum wire cross section 2 5 mm2...

Page 8: ...uorescent lamps non compensated 3680 W parallel compensated 2500 W 200 F series compensated 3680 W 200 F Compact fluorescent lamp CFL non compensated 3680 W parallel compensated 2500 W 200 F High pres...

Reviews: