S
E
TTING
Manual Datalogger SenNet DL150 / DL151 / DL170 / DL171 / DL172
Versión 1.01
Satel Spain
61
▪
Street
Lighting:
select if the application is for street lighting.
▪
CSV name format
: name format of the CSV files.
▪
CSV fields
: indicate the list of the range of files that are going to be stored in the CSV. Click on
the interrogation (?) to see the format.
▪
Management Platform
: the type of the platform to send the data.
▪
List of devices
: table that contains one record per device. The columns of the table are:
▪
Type of device
. Select displaying the list of available.
▪
Comm id
: (physical identifier of the communications): the id for communications.
o
If it is a device with Modbus RTU protocol, the Comm id will be the Modbus id (e.g. the
devices 'SenNet 4Input-4Output-RF','SenNet 4Input-4Output RS485' or
‘SenNet
4analog-input-RF').
o
If it is a meter with IEC 870-5-102 protocol, the id will be the link address, etc.
o
If it is a device that forms part of the SenNet radio network, you should write the serial
number included on the label of the device (e.g. the devices 'SenNet CO2-RF','SenNet
PC-RF', 'SenNet THL-IM' or 'SenNet T-RF').
o
Click on the symbol "?" for further details.
▪
App id
(application identifier): it is the id with which you want the data to be sent to the
platform. It is also used to store the data in CSV files if wanted. Usually, devices are assigned
the numbers 1, 2, 3... n in the order in which they are appearing. Click on the symbol "?"
for
further details.
▪
Communication params
: here you should indicate the port through which the device is
connected to the datalogger. The valid options are:
RS232, RS485, RF,
an IP address or a port in
the form
IP / port
. You can also indicate the communications parameters: 9N81, 9600 bps, No
parity, 8 data bits, 1 stop bit.
Contact the technical department of Satel Spain for each specific device. In the case of the
SenNet RF network you should indicate the serial number of the radio peripheral after RF. For
example RF2030. Click on the symbol "?" for further details.
▪
Name
: name of the device to be shown in the screen 'datos capturados'. Click on the symbol
"?" for further details.
▪
Additional param
: specific parameters of the device. For example, for an internal electricity
meter here you should write the nominal current of the current transformer that is going to be
used. Click on the symbol "?" for further details. For the internal meters the valid values
are 5,
50, 100, 150, 400, 800 or 5000.
▪
Box
Able
. To enable / disable the device.
Figure 35. Overview of the application parameters menu