The SP-4006 BL siren has the two indicator LEDs situated on the opposite ends of housing
sides, which are blinking alternately 1 s / 1 s when supply voltage is available at the +12V
input. This function cannot be disabled.
The SP-4006 BL siren has an indicator LED situated in the middle of the lower edge of
enclosure. The LED is blinking when supply voltage is present at the +12V input. Removal of
the jumper designated as
LED
will disable the LED function.
3. Connection
There are two types of alarm outputs which are used in alarm control systems: common
ground outputs and common supply outputs. The siren can be activated by any type of
output, provided that suitable connections are made.
Note:
The converter supplying the acoustic siren system generates a very high voltage
which can cause electric shock when touched. Hence, all connections may only be
made when the battery is disconnected and the +12 V wire is to be connected last.
INTEGRA 32
STO
TMP
SENS. TMP
TMP
STA
SP-4006
GND +12V
R
Fig. 2. Way of connecting the SP-4006 siren to the alarm control panel without a resistor in
the siren tamper circuit. The OUT2 high-current output is programmed as the supply one.
The OUT3 and OUT4 low-current outputs control the signaling (OUT3 will trigger the acoustic
signaling, and OUT4 – optical).
The Z1 zone is programmed as tamper, NC type.