background image

 SATEL 

SPLZ-1011 

2

After installing the siren, it is recommended to seal the mounting holes and the cable entry 
with silicone compound. 

3. 

Operation of siren

 

The way of activating the SPLZ-1011 is different from that of the SPLZ1010B siren 
(read carefully the text below). 

The SPLZ-1011 can operate with any source of alarm signal. The circuits for acoustic and 
visual signaling have separate control inputs. The acoustic signaling is controlled by the STA 
input, while the visual signaling – by the STO input. Signaling is triggered after a change of 
voltage polarity from 0V to 12V or from 12V to 0V.  

Note: Alarm will be triggered also in case of stable signal loss at control input, e.g. after 

cutting off the cable. 

The way of changing voltage polarity for the purpose of triggering the alarm is set by means 
of the jumpers PLA and PLO

The siren has been designed so as to be inactive on connecting power supply to it, 
irrespective of the status of inputs STA and STO. Only after elapse of 20 seconds in the 
stable, inactive state (constant power supply from the control panel and voltage on inputs 
which does not trigger alarm) it is possible to trigger the signaling. After each switching the 
power supply off and on, the time is counted over again. This function allows an accidental 
activation of the device to be avoided during installation of the system.  

The test mode makes it possible to activate signaling without the need to wait for 20 
seconds. In order to do so, remove the jumper O+A,  switch the siren on and, within 5 
seconds, put the jumper on again. 

The SAB  terminals are used for connecting the siren to the tamper circuit of the alarm 
system. When the siren is correctly mounted and the contacts of onboard switches are 
closed, the SAB terminals are shorted, too. 

The siren is adapted for operation with a 6 V battery installed (back-up power supply). 

The external power supply should be connected to the terminals +12V and GND. The loss of 
voltage on these terminals will trigger a tamper alarm, the duration of which depends on the 
settings of jumpers TM0 and TM1. The kind of signaling is set with the jumper O+A
Restoration of the supply voltage will cancel the tamper alarm. Having mounted the siren, 
check the performance of this function by disconnecting and reconnecting the power supply 
voltage. 

Note: The  jumpers  TM0,  TM1 determine the maximum active time of acoustic signaling. 

Afterwards, irrespective of the value set on the control panel, the siren will go silent. 
Signaling can only be triggered again after the STA input voltage returns to the state 
corresponding to the PLA jumper "no alarm" setting. 

The LED placed on electronics board blinks when the +12V input power voltage is applied. 
The LED can be switched off by removing the JP8 jumper.  

4. Connection 

There are two types of alarm outputs which are used in alarm control systems: common 
ground outputs and common supply outputs. The siren can be activated by any type of 
output, provided that suitable connections are made. If the control panel alarm outputs have 
no resistors

 

which induced polarization,

 

then, in order to ensure proper operation of the 

device, it is necessary to connect 2,2k

 resistors as shown on figure 2, 3 or 4 (depending on 

the output type). They can be connected in the control panel or in the siren.

 

Such resistors must also be connected for outputs with load control. 

 

Reviews: