3
S
TEAMCORE
Requirements for Proper Installation
1.) Use copper or brass fittings only. (NEVER USE GALVANIZED
FITTINGS)
2.) The water inlet
,
steam outlet, and drain need brass unions for
easy removal.
3.) The Generator must be upright, accessible, and on a level surface.
4.) Unit may be installed up to 50 feet away from shower area.
5.) DO N
NOT use ABS, PVC or any plastic material for the steam line.
6.) DO N
NOT plumb a trap in the steam or drain line.
7.) Pitch steam line back toward generator and avoid perfectly level
plumbed lines.
8.) Before connecting water line to the generator, flush water line
into a five gallon pail to remove any slit or other materials that may
be in the line. An in-line water filter is recommended.
9.) Make sure water is turned on to the unit before testing or
operating the unit.
10.) Unit and Supply lines MUST be protected from freezing!
Parts Enclosed
Control
Steamhead
Steam Generator
Pressure Relief Valve, coupling, & fittings.
Tools Needed
•Pipe Wrench
•Tubing Cutter
•Flaring tool (if flared fittings are used)
•Pipe thread cap
•Adjustable wrench
•Screwdrivers (Phillips and Regular)
•Solder & Flux
•Drill motor
•Propane Torch
•Silicone Gun
•Other tools as required
All generators are designed to build NO P
PRESSURE during
operation.
This is for your safety.
Generator Installation Instructions
Typical Residential Model
Typical Commercial Model
CAUTION: If the unit is run without water, serious
damage may occur! This possible damage is not
covered under the limited warranty.
NOTE: Failure to follow installation instructions
specificaly will cause the warranty to be void.