INSTALLATION OF THE GENERATOR AND OPTIONAL EXTRAS 
 
 
 

 
 
 
Control module

 may be installed inside the steam room. If the control module is fitted outside the 

steam room or so low within the steam room that its own thermostat does not show the correct 
temperature, a separate thermostat which is connected directly to the circuit board must be used. It 
must be mounted at a height of 170cm from floor level and preferably opposite the door  
(see illustration). 
 
When the 

push button

 is used, the provided limiting thermostat must 

always

 be installed, to ensure 

the temperature does not rise above +50 °C. See the separate installation and connection diagrams. 
 

Steam nozzle(s)

 must be fitted approx. 20 - 40 cm from the floor either under the seat or on the 

wall in a position such that hot steam cannot burn the feet. When fitting nozzles, one must also 
ensure that they cannot be inadvertently touched. 

The temperature of the steam is +100

 

°C 

and it 

can cause burns. 
 
The 

thermostat

 is fitted at a height of 170 cm from floor level and preferably on the wall opposite 

the door. 
The hole for the thermostat should be sealed with silicone or similar to prevent moisture ingress to 
the wall. The thermostat is connected directly to the circuit card of the generator. 
 (see connection diagram.)

 

 
 
 

Water 
connection

400V 3N~

Floor drain

Temperature sensor

Control module

Steam nozzle

O K

ON         OFF

O K

ON         OFF

Pressure button

Summary of Contents for HELO HSS M 34

Page 1: ...1 SAUNATEC GROUP Ltd HELO HSS M and HST M STEAM GENERATOR User and Installation Guide for models HELO HSS M 34 47 60 77 HELO HST M 90 120 140 314 SHS 64 C...

Page 2: ...gramme Automatic fill and water level setting Floor or wall mounting Digital control module Temperature control Time control Light control Control module may be fitted on inside or outside of steam ro...

Page 3: ...ures above and to the sides is no less than 30 cm Consider the space needed around the generator for routine maintenance For the emptying of the tank there should be drainage available in the vicinity...

Page 4: ...pe MUST NOT include traps as the water which collects will cause restricted steam flow and spitting at the steam head Any water from condensation in the pipe must be allowed to flow freely back into t...

Page 5: ...oning and good ventilation may also need more power The required power can be estimated using the following formula Capacity m3 x K1 x K2 Required power kW Ventilation K1 0 75 No ventilation K1 0 52 A...

Page 6: ...1 N 3 N N N N N V2 V1 H1 H2 N L PE OLEA 72 S1 S2 High level Water valve drain 230 V AC Water valve filling 230 V AC Heater fuse Elements Contactor LC1 LC2 B1 B2 T1 T2 A K S1 S2 TX RX 5 0 Serial traffi...

Page 7: ...5 0 354 SHS 33 A 1 5 2 6 Level probe Earthing for cover High level Water valve drain 230 V AC Water valve filling 230 V AC Heater fuse Elements Contactor Serial traffic to MIDI control On Off Push but...

Page 8: ...230 V AC Water valve filling 230 V AC Thermofuse Contactor LC1 LC2 B1 B2 T1 T2 A K S1 S2 TX RX 5 0 Control keyboard On Off pushbutton Thermostat Alarm 12 V DC Light control opto max 24 V DC 50 mA 1 6...

Page 9: ...the separate installation and connection diagrams Steam nozzle s must be fitted approx 20 40 cm from the floor either under the seat or on the wall in a position such that hot steam cannot burn the fe...

Page 10: ...ashing Bathing time selection button time display flashing plus button for increasing the setting of time and temperature minus button for decreasing the setting of time and temperature Light control...

Page 11: ...ed to LC1 When the lights button is pressed a transistor on the circuit board transfers the voltage into LC2 which carries out the actual light unit control PUSH BUTTON Functions of the button When st...

Page 12: ...ite is designed to clip fit onto the control housing This bezel is removed with the supplied tool Using this tool lightly press the locking pin in each of the 4 holes around the perimeter whilst pulli...

Page 13: ...he flush and rinse After the cycle has run the generator will await a new start up command ELECTRIC FLUSHING VENT Drain Kit M Optional extra HSS M and HST M generators flushing vent installation Use P...

Page 14: ...removal of lime from the tank Testing water quality and de scaling for HSS M and HST M generators Test strips included in the test pack supplied with the generator are used as follows Submerge the tes...

Page 15: ...n fitted with an automatic or a manual flushing valve Automatic flushing valve The generator will empty and rinse itself after 15 minutes of idle time After the first flush generator is started again...

Reviews: