6 Boiler Location, Flue and Ventilation
6.1 Location
This boiler is not suitable for outdoor installation.
This boiler may be installed in any room, although particular
attention is drawn to the installation of a boiler in a room
containing a bath or shower where reference must be made to
the relevant requirements.
The boiler must
NOT
be installed in a cupboard.
In GB this is the current I.E.E. WIRING REGULATIONS and
BUILDING REGULATIONS.
In IE reference should be made to the current edition of I.S.813
"Domestic Gas Installations" and the current ETCI rules.
The boiler must be mounted on a flat wall, which is sufficiently
robust to take its weight,
see diagram 1.1
.
6.2 Clearances
The position of the boiler must be such that there is adequate
space for servicing.
The recommended clearances are shown in
diagram 6.1.
The minimum acceptable spacings from the terminal to
obstructions and ventilation openings are shown in
diagram
6.2.
For Ireland the minimum distances for flue terminal
positioning must be those detailed in I.S.813 "Domestic Gas
Installations".
The terminal must be exposed to the external air, allowing free
passage of air across it at all times.
Being a condensing boiler some pluming may occur from the
flue outlet. This should be taken into consideration when
selecting the position for the terminal.
Carports or similar extensions of a roof only, or a roof and one
wall, require special consideration with respect to any openings,
doors, vents or windows under the roof. Care is required to
protect the roof if made of plastic sheeting. If the carport
comprises of a roof and two or more walls, seek advice from the
local gas supply company before installing the boiler.
Diagram 6.1
11901
Diagram 6.2
MINIMUM SITING DIMENSIONS FOR THE
POSITIONING OF FLUE TERMINALS
MM
HORIZONTAL FLUES
A
DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR BRICK,
OPENING WINDOWS, AIR VENT, OR ANY
OTHER VENTILATION OPENING
300
B
BELOW GUTTER, DRAIN/SOIL PIPE
75
C
BELOW EAVES
200
D
BELOW A BALCONY OR CAR PORT
200
E
FROM VERTICAL DRAIN PIPES AND
SOIL PIPES
150
F FROM INTERNAL/EXTERNAL CORNERS
OR TO A BOUNDARY ALONGSIDE THE
TERMINAL
300
G
ABOVE ADJACENT GROUND OR
BALCONY LEVEL
300
H
FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL
600
I
FACING TERMINALS
1200
J
FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING
1200
K
VERTICAL FROM A TERMINAL
1500
L
HORIZONTALLY FROM A TERMINAL
300
VERTICAL FLUES
M
FROM ADJACENT WALL TO FLUE
300
N
FROM ANOTHER TERMINAL
600
P
FROM ADJACENT OPENING WINDOW
1000
Q
ABOVE ROOF LEVEL
300
11508
5mm
25mm
ABOVE
ELBOW
25mm
300mm
600mm
TERMINAL
GUARD
Summary of Contents for EnviroPlus F24e
Page 18: ...18 2000225294A Diagram 5 1 11907 5 Boiler Schematic F24e F28e ONLY ...
Page 19: ...19 2000225294A 5 Boiler Schematic Diagram 5 1a 12248 BYPASS F28e SB ONLY ...
Page 49: ...49 2000225294A 14 Fault Finding 12410 Diagram 14 4 ...
Page 51: ...51 2000225294A 15 Wiring Diagram Diagram 15 1a 12240 F28e SB ONLY ...