36
2000225294A
INTERNAL SOIL
AND VENT STACK
BOILER
MIN. DIA. 21MM
NO RESTRICTION
ON LENGTH
EXTERNAL SOIL
AND VENT STACK
MIN. DIA. 21MM
NO RESTRICTION
ON LENGTH
BOILER
BOILER
MIN. DIA. 21MM
EXTERNAL LENGTH
OF PIPE 3M MAX.
OPEN END OF PIPE
DIRECT INTO GULLEY
BELOW GROUND BUT
ABOVE WATER LEVEL
MIN. DIA. 21MM
NO RESTRICTION
ON LENGTH
BOILER
SINK
(CONSTITUTES
AIR BREAK)
BOILER
MIN. DIA. 21MM
NO RESTRICTION
ON LENGTH
SINK
OPEN END OF PIPE DIRECT INTO
GULLEY BELOW GROUND LEVEL
BUT ABOVE WATER LEVEL.
21MM TERMINATION FROM APPLIANCE
*NOTE: FOR EXTENDED PIPE RUNS 32MM DIA.
PIPE SHOULD BE USED.
2.5 FALL
o
25MM
CEMENT MORTAR SEALING
BOTTOM OF TUBE SEALED
100MM PLASTIC TUBE
300MM
HOLE DEPTH
400MM
2 ROWS OF 3 x 12MM
HOLES AT 25MM CENTRES
50MM FROM BOTTOM OF
TUBE. HOLES TO FACE AWAY
FROM HOUSE.
External Soil and Vent Pipe or Rainwater Pipe
Internal Soil and Vent Pipe
External Termination into Soakaway
Internal Termination Downstream of
Sink Waste
Internal Termination into Combined Sink Waste
External Termination to a Gulley or Hopper
*
NOTE: PIPEWORK SHOULD ALWAYS FALL AWAY FROM BOILER BY AT LEAST 2.5
0
EXTERNAL
MAX. 3M
*NOTE: FOR EXTENDED
PIPE RUNS 32MM DIA.
PIPE SHOULD BE USED.
12333
Diagram 10.3
10 Safety Discharge Valve and Condensate Connections
Summary of Contents for EnviroPlus F24e
Page 18: ...18 2000225294A Diagram 5 1 11907 5 Boiler Schematic F24e F28e ONLY ...
Page 19: ...19 2000225294A 5 Boiler Schematic Diagram 5 1a 12248 BYPASS F28e SB ONLY ...
Page 49: ...49 2000225294A 14 Fault Finding 12410 Diagram 14 4 ...
Page 51: ...51 2000225294A 15 Wiring Diagram Diagram 15 1a 12240 F28e SB ONLY ...