44
Description
Unit
SEMIA CONDENS
F24 E
SEMIA CONDENS
F30 E
Dimensions:
Height
mm
750
750
Width
mm
400
400
Depth
mm
347
347
Net weight
kg
41.5
43
Supply voltage
V/Hz
230/50
230/50
Maximum absorbed power
W
145
150
Electric protection
IP X4D
IP X4D
CE number
0694 BN 3710
0694 BN 3710
Technical data
depending on the gas type
Unit
SEMIA CONDENS
F24 E
SEMIA CONDENS
F30 E
Natural gas G 20 (1)
Flow rate at maximum input
m
3
/h
2.71
3.12
Flow rate at minimum input
m
3
/h
1.11
1.27
Inlet pressure
mbar
20
20
Burner injector diameter
mm
1.25
1.30
(1) 15 °C, 1013,25 mbar
16.1 Burner
pressure
tables
SEMIA CONDENS F24 E
HEAT OUTPUT
PRESSURE
kW
Btu/hr
mbar
9.5
32566
2.1
10
34120
2.3
11
37532
2.7
12
40944
3.2
13
44356
3.7
14
47768
4.3
15
51180
4.9
16
54592
5.5
17
58004
6.1
18
61416
6.8
19
64828
7.5
20
68240
8.2
21
71652
9.0
22
75064
9.8
23
78476
10.6
24
81888
11.4
24.5
83594
11.6
SEMIA CONDENS F30 E
HEAT OUTPUT
PRESSURE
kW
Btu/hr
mbar
11.1
37832
2.2
12
40944
2.6
13
44356
3.0
14
47768
3.4
15
51180
3.9
16
54592
4.4
17
58004
4.9
18
61416
5.5
19
64828
6.1
20
68240
6.7
21
71652
7.3
22
75064
7.9
23
78476
8.6
24
81888
9.3
25
85300
10.0
26
88712
10.8
27
92124
11.5
28
95536
12.3
28.6
97735
12.7