TFL 611: Continuous frost monitor with capillary sensor 

How energy efficiency is improved 

Demand-led, large-scale monitoring of installation parts with fully active sensor. 

Areas of application 

Temperature monitoring in air/water heat exchangers and air ducting with constant frost-protection 
control, frost-protection switch and temperature transmission. For applications on the air side of instal-
lations. 

Features 

 

Measuring range: 0 to 15 °C  

 

Frost point can be adjusted 

 

Contact rating: 5 mA, 5 V to 6 A, 250 V 

 

Start-up function 

 

LED display indicating risk of frost 

 

Selectable block on switching on again 

 

< 40 s time constant with moving air 

 

2 or 6 m copper capillary tube 

Technical description 

 

Two-part plastic housing 

 

Ambient temperature: –15 to +60 °C  

 

Controlled housing heating to safeguard measured variable 

 

IP 42 

 

Active from 25 cm capillary length in switching temperature 

 

 

Operation 

Using a vapour-filled  capillary tube and diaphragm system, the frost monitor measures the lowest 
temperature that occurs anywhere along at least 250 mm of the capillary tube. 
If the monitor is correctly positioned at the air outlet of the heating coil, it measures the lowest temper-
ature even if there are strata of differing air temperatures. In so doing, the steam pressure causes a 
movement of the diaphragm capsule in the capillary tube. By means of an inductive measuring sys-
tem, this movement is converted into an electric signal and is amplified electronically; it then creates a 
0...10 V d.c. measuring signal. 

 

 

X

s

T

Y

10V

B10592

1

2

3

1

2

3

X

Sd

0V

 

T

Y10162

 

Type 

Capillary tube 

Setting  

range X

S

 

°C 

Switching 

diff. X

Sd

 

Permissible 

sensor temp. 

°C

 

Weight  

 

kg 

 

TFL 611 F200 

1)

 

2 m 

1...10 

–15...110 

0.34 

 

TFL 611 F600 

1)

 

6 m 

1...10 

–15...110 

0.41 

 

 

 

 

 

 

 

Power supply 

24 V~, ± 20% 

Active capillary length 

3) 

min. 250 mm 

Power consumption 

6 VA 

Factory setting 

5 °C 

Measuring range of sensor 

0...15 °C / 0…10 V= 

Temp. at head of instrument 

4) 

–15...60 °C 

Control signal output 

0...10 V=, max. ± 1 mA 

Degree of protection 

IP 42 (EN 60529) 

Max. length of cable at 1,5 mm

300 m 

Protection class 

II (IEC 60730) 

Control signal input 

0...10 V=, max. ± 0,1 mA   

 

Contact rating 

 

Wiring diagram 

A10390

 

maximum 

2) 

6(4) A, 250 V~ 

Dimension drawing 

M10422

 

minimum  

5 mA, 5 V~/= 

Fitting instructions 

MV 505954 

Time constant 

 

 

 

in still air 

90 s 

 

 

in moving air 

40 s 

 

 

 

 

 

 

 

 

Accessories 

 

0292146 001

* 

Set for duct fitting consisting of: 5 capillary-tube holders, 1 depth adjustable flange 

 

0303167 000

* 

5 capillary-tube holders 

 

0374534 001

* 

Depth adjustable flange 

 

 

 

 

*)

 

Dimension drawing or wiring diagram are available under the same number 

 

 

 

 

 

 

 

1)

 

The accessory 0292146 001 for duct fitting must be ordered separately. 

2)

 

If under inductive load, take RC circuit into account. 

3) 

The monitor always reacts to the coldest place (minimum length is 250 mm). 

4) 

The head of the instrument is frost protected for ambient temperatures up to max. -15 °C by a heating system. 

 

 

7122040003  06 