Use the diagram below when wiring the 10K temperature sensors.
Thermistor Connections
Making Connections
Power Connections
RS-485 Connections
Refer to the following documents located on the
Savant Customer
Community
for additional information.
– Multistat Smart Thermostat Deployment Guide (009-1636)
– Multistat Thermostat with Touchscreen (009-1593)
Additional Information
< 1/8 inch of
bare wire
exposed
When making connections, follow the guidelines set below to ensure a
safe and secure connection.
Use the diagrams below when making the power connections be-
tween the thermostat and the CLI-10K4IN climate module.
Use the diagrams below when making the RS-485 connections be-
tween the thermostat and CLI-10K4IN climate module.
– Power can be daisy-chained between modules.
– The cable lengths vary depending on the size of the wire. See the
specifications table on page 1 for more information.
– Supports a maximum of four sensors per CLI-10K4IN module.
– There is no polarity to the 10K temperature sensors.
– Max cable length = 500 feet (152.4 meters).
– Minimum size wire = 24 AWG.
– A twisted pair is recommended (e.g. Cat 5e/6/7).
– Any 10K type temperature sensor is supported. See the
– Climate modules can be daisy-chained to increase the number of
sensors.
– Two or more ports can be combined and the average of these
sensors taken.
1. With a small slotted screwdriver,
turn the screws on the connector
counterclockwise (CCW) until the
silver crimps open enough to slide
a wire into the square slots.
2. Strip back insulation on each wire
to
1
/4
inch and insert the stripped
wire into the proper connection.
3. Turn the screw clockwise (CW)
until the crimps tighten around
each wire. Tug on each wire a bit
to verify they are secure.
o
G
AUX
OUT
AUX
IN
RS2
RS1 GND
GND
R
X-
RX+
GND
1-
WIRE
5V
DC
Y2
Y1
W2
W1
RC
RH
TX+ TX- 24C
10K
Status
CLI-10K4IN-00
S/N:
UID:
SHR180600332
001AAE09C6240000
1
2
3
4
24VAC
~
~
+
+
+
+
Power can be
daisy-chained
to other modules
24V AC
from HVAC
o
G
AUX
OUT
AUX
IN
RS2
RS1 GND
GND
GND
R
X-
RX+
GND
1-
WIRE
5V
DC
Y2
Y1
W2
W1
RC
RH
TX+
(TX+)
TX-
(TX-)
24C
Left Side View
RS-485 Cable
CLI-10K4IN
10K Remote
Sensors
10K
Status
CLI-10K4IN-00
S/N:
UID:
SHR180600332
001AAE09C6240000
1
2
3
4
24VAC
~
~
+
+
+
+
– Max cable length is 1000 feet (304.8 meters).
– Savant recommends using standard RS-485 cable for wire runs.