background image

CLI-8000  |  009-1090-03  |  161006

Copyright© 2016 Savant Systems, LLC

45 Perseverance Way, Hayannis, MA 02601

Savant.com

  | 508.683.2500

Thermostat Processing Unit (TPU)

CLI-8000-xx

Quick Reference Guide

Box Contents

(1) CLI-8000-xx (Includes all connectors for front panel)

(1) Quick Reference Guide (this document)

Related Components

Savant Host

Savant Controller

External 120V AC to 24V AC Transformer (PWR-2440-xx)

Optional Remote Sensors

SST-TEMP1 - Remote Indoor Sensor

SST-OTEMP1 - Remote Outdoor Sensor

CLI-THFM1 - Remote Humidity/Temperature Smart Sensor

CLI-PLEN1C - Commercial Plenum Sensor (Heat duct sensor)

CLI-PLEN1R - Residential Plenum Sensor (Heat duct sensor)

CLI-SLAB1 - Slab Sensor (Floor Heating Sensor)

Note

: Each zone on the CLI-8000 supports communications with up 

to four temperature sensors including two humidity sensors.

For Product Info

Specifications

Environmental

Temperature

32° to 104° F (0° to 40° C)

Humidity

10% to 90% (non-condensing)

Dimensions and Weights

Height

without Cover

with Cover

11.05 in (280.67 mm)

12.17 in (309.12 mm)

Width

14.23 in (361.44 mm)

15.48 in (393.19 mm)

Depth

2.71 in (68.83 mm)

2.81 in (71.37 mm)

Weight

Net

Shipping

8.75 lb (4.00 kg)

12.00 lb (5.43 kg)

Power

Power (Input)

24V AC (40AV) from external transformer

Power Draw 

(Maximum)

12W @ 24V AC

Cable Requirements

Relay Bank to 

HVAC system

18 American Wire Gauge (AWG)

Standard HVAC wiring 

(RH, RC, W1, W, Y1, Y2, O, G, Aux)

Cable Requirements (Sensors)

Data Sensor 

Bus (1-Wire)

24 AWG (Cat 5) 600 feet 

(182 m) maximum (cumulative)

Remote Sensor

24 AWG (Cat 5) 500 feet (152 m) maximum

Compliance

Safety and 

Emissions

FCC Part 15

RoHS

Compliant

Additional info

RS-232

Baud Rate = 19200

Front Panel

Item

Description

A

Ethernet

Reserved for Future Use

B

HVAC Relays

Each relay bank or zone gets wired to an HVAC 

system. Supports wiring up to eight individual 

HVAC systems.

C

RS-232

Connect cable from the RS-232 port to a Sa-

vant Controller. (Communication between the 

controller and the CLI-8000 is achieved over 

the RS-232 connection.) RS-232 supports 19200 

baud.

D

Station Bus

Reserved For Future Use

E

Console

Mini USB (Mini-B) female connector 

(Serial UART); Debug terminal

F

DSB/1-Wire

Connects to the Data Sensor Bus, which is a 

serial bus based on the 1-Wire protocol. The 

CLI-THFM1 smart sensor communicates over the 

Data Sensor Bus through this connection. Up to 

two smart sensors per zone can be configured 

with a total of eight per system.

G

Display/Keypad

To monitor and configure the system. Use the 

keypad to scroll through the available menus 

and configure each zone.

H

Remote Sensors

For Indoor, Outdoor, Slab, and Plenum two-wire

temperature sensors. A maximum of two per 

zone is supported.

 I

Input Power 

(Access)

Remove the power input access screw and 

remove the associated panel. This will give user 

access to the power supply board for wiring the 

24V AC input power.

J

Zone LEDs

Indicates which zone has been

selected via the keypad for configuration.

K

Input Power 

(24V AC)

System is powered by 24V AC power source. 

Power cable is fed through ½ inch cable re-

straint (not included) installed at bottom of box. 

Input power is wired to a two position screw 

terminal block on the power supply board.

L

Analog Control

Reserved for Future Use

M

USB

Reserved for Future Use

N

Smart Connect

Maintenance functions such as firmware up-

grades are achieved through the Smart Connect 

connection. Requires SCA-CONF-xx or SCA-

CONFL-xx Smart Connect cable.

Reviews: