background image

CLI-PTAC1K1-00  |  009-1806-00  |  190613 

Copyright 2019 Savant Systems, LLC

45 Perseverance Way, Hyannis, MA 02601 

Savant.com

  |  508.683.2500

2     of     2

Relay Connections

10K Remote Sensor Connections

RS-485 Connections

Making Connections

Power Connections

Refer to the following documents located on the 

Savant Customer 

Community

 for additional information.

 

– Multistat Smart Thermostat Deployment Guide (009-1636)

 

– Multistat Thermostat with Touchscreen QSG (009-1593)

Additional Information

1.  With a small slotted screwdriver, turn 

the screws on the connector counter-

clockwise (CCW) until the silver crimps 

open enough to slide a wire into the 

square slots.

2.  Strip back insulation on each wire to 

1

/4

 

inch and insert the stripped wire 

into the proper connection.

3.  Turn the screw clockwise (CW) until 

the crimps tighten around each wire. 

Tug on each wire a bit to verify they 

are secure.

< 1/8 inch of

bare wire

exposed

When making connections, follow the guidelines set below to ensure a 

safe and secure connection.

Use the diagrams below when making connections between the relay 

outputs and the connections at the HVAC equipment.

Use the diagrams below when making connections between the 10K 

remote sensor port and a 10K remote sensor.

Use the diagrams below when making the power connections be-

tween the thermostat and the CLI-PTAC1K1 climate module.

o

G

AUX 
OUT

AUX 
IN

RS2

RS1 GND

GND

R

X-

RX+

GND

1-

WIRE

5V 
DC

Y2

Y1

W2

W1

RC

RH

TX+ TX- 24C

PTAC

Status

W1

W2

Y1

CLI-PTAC1K1-00

S/N:

UID:

SHR180601332

001AAE09CA340000

Y2

G
O

10K

C

R

+

Power can be 

daisy-chained

to other modules

24V AC 

from HVAC

 

– Power should only be connected across terminals C and R as 

shown in the diagram above. The input power across the C and R 

terminal supplies the voltage to power the module as well as all the 

climate relays. 

 

– Power can be daisy-chained between modules.

 

– The cable lengths vary depending on the size of the wire. See the 

specifications table on page 1 for more information.

 

– There is no polarity to the 10K temperature sensors.

 

– Minimum size wire = #24 AWG.

 

– Maximum cable length = 500 feet (182meters).

 

– A twisted pair is recommended (E.G. cat 5e/6/7)

 

– All 10K type temperature sensors available through Savant are sup-

ported. See the 

Supported Sensors

 section.

 

– Use only HVAC approved cabling to make the connections.

 

– The CLI-PTAC1K1 also supports PTAC Heat Pump type installations.

 

– Savant recommends using standard RS-485 cable for wire runs.

 

– Max cable length is 1000 feet (304.8 meters).

o

G

AUX 
OUT

AUX IN

RS2

RS1 GND

GND

GND

R

X-

RX+

GND

1-

WIRE

5V 
DC

Y2

Y1

W2

W1

RC

RH

TX+

(TX+)

TX-

(TX-)

24C

Left Side View

RS-485 Cable

CLI-PTAC1K1

Use the diagrams below when making the RS-485 connections be-

tween the thermostat and CLI-PTAC1K1 climate module.

PTAC

Status

W1

W2

Y1

CLI-PTAC1K1-00

S/N:

UID:

SHR180601332

001AAE09CA340000

Y2

G
O

10K

C

R

+

10K Remote

Sensor

W1

1st Stage 

Heat

2nd Stage 

Heat

PTAC SYSTEM CONNECTIONS

Compressor 

1st Stage

Compressor 

2nd Stage

Fan Relay

Reversing

Valve

W2

Y2

Y1

G

O

PTAC

Status

W1

W2

Y1

CLI-PTAC1K1-00

S/N:

UID:

SHR180601332

001AAE09CA340000

Y2

G
O

10K

C

R

+

Reviews: