background image

Super Vision International 

• 

8210 Presidents Drive 

• 

•Orlando, Florida 32809 •

 407.857.9900 

• 

Fax 407.857.0050 

• 

www.svision.com

Super Vision International 

• 

8210 Presidents Drive 

• 

•Orlando, Florida 32809 •

 407.857.9900 

• 

Fax 407.857.0050 

• 

www.svision.com

leD aCCessory ConneCTions

Twist the white wire of the M4 controller with the incoming “neutral” (not the ground) 
wire.  Secure as in “step (4)” (

see FIGURE 3a

).

Repeat for the green ground wire and the incoming ground wire (

see FIGURE 3a

).

Carefully tuck the wires into the area below the power supply while being careful 
that the wires do not lay against the internal components of the power supply.
If possible, verify a grounding path exists between the incoming service ground wire 
and the case of the M4 controller.  If this is not possible, double check the ground 
connection between the crimp and/or wire nut connection and the case of the M4 
controller.

V. LED ACCESSORY CONNECTIONS 

(Savi notes or X-Stream LED Modules)

Locate the incoming cable for fixture #1 (

see FIGURE 2

).  This cable will be at-

tached to terminal block J5 on the PCB.  Trim excess cable leaving no more than six 
(6) inches protruding from the conduit.
Carefully remove two (2) inches of insulation from the cable (a box cutter set to pro-
trude less than 1/8” is good for this purpose).  Cut from the desired removal location 
towards the cut end of the cable to prevent damaging the internal wires.
Separate the insulation along the cut path and fold it back.  Using cutters remove 
the excess cable insulation.  Only the four internal wires should be remaining (red, 
green, blue, and a fourth conductor - usually black).
Using the wire stripper, remove 1/8 to 3/16” of insulation from each of the four 
wires.
The wires will be installed as shown in 

FIGURE 3b

 below.  

Insert each wire into the appropriate terminal block location.  Using a small flat 
blade screwdriver, tighten each screw of the terminal block until you feel it com-
press the wire and become difficult to turn (approximately 3.5 in-lbs).   

DO NOT OVERTIGHTEN

.  Carefully pull on the wire to verify it is secure.

5.

6.
7.

8.

1.

2.

3.

4.

5.

6.

DUE TO ThE DESIRED WATER RESISTAnT SEAL OF ThE EncLOSURE, DO nOT RE-
MOvE Any knOckOUTS UnLESS ThAT hOLE WILL hAvE A cOnDUIT InSTALLED.  
IF  A  knOckOUT  IS  AccIDEnTALLy  REMOvED,  STEPS  MUST  BE  TAkEn  TO  RE-
SEAL ThE OPEnInG OR ThE M4 cOnTROLLER WILL BE DAMAGED.

WARNING

8

LED outputs must be connected as 

shown to avoid damage to the circuit

Red
Black

Green

Blue

LED FIXTURE CONNECTION TO TERMINAL BLOCK

#1

#2

#3

#4

FIGURE 3b

#1 Position 

- Power Wire (usually Black)

#2 Position

 - Red wire

#3 Position

 - Green wire

#4 Position

 - Blue wire

Summary of Contents for SAVI-NOTE150

Page 1: ...tallation Manual Super Vision International 8210 Presidents Drive Orlando Florida 32809 407 857 9900 Fax 407 857 0050 www svision com SaVi Note Underwater LED Light SAVI NOTE75 SAVI NOTE150 Model Numb...

Page 2: ...ision International 8210 Presidents Drive Orlando Florida 32809 407 857 9900 Fax 407 857 0050 www svision com Table of Contents Safety Precautions 2 SaVi Note Install Instructions 3 4 M4 Instructions...

Page 3: ...outed by approved methods to conduit fittings on the box For DMX based units do not install data cables in the same conduit as power cables to prevent communication problems Be sure the mounting surfa...

Page 4: ...is not used for swimming and the lens is adequately guarded to prevent any person from contacting it STEP 2 Snake the 4 conductor electric cord through the conduit outlet of the wall fitting into the...

Page 5: ...900 Fax 407 857 0050 www svision com INSTALLATION Instructions 4 STEP 3 Using the lens wrench thread the fixture into the wall fitting until it is snug STEP 4 Wire the fixture to the M4 Controller See...

Page 6: ...5 Installation Manual M4 LED Controller For SaVi Notes and X Stream LED Modules M4 L M4 H M4 L DMX M4 H DMX Model Numbers...

Page 7: ...to complete the mounting of the M4 controller III Conduit and Ground Connections 1 After selecting the desired conduit size or carefully remove the appropriate knock outs in the bottom of the enclosur...

Page 8: ...troller It will be located under the power supply and will consist of one black 120 VAC one white neutral and one green safety ground wire Locate the incoming power wires from the conduit Trim excess...

Page 9: ...is good for this purpose Cut from the desired removal location towards the cut end of the cable to prevent damaging the internal wires Separate the insulation along the cut path and fold it back Usin...

Page 10: ...tions Determine if the installation uses an input or both an input and an output DMX con nection An additional output connection can be added in the future if desired Locate the incoming DMX communica...

Page 11: ...fety of all Once satisfied that all appropriate prepara tions are complete proceed to the steps below To check the system it is necessary for someone to monitor the output of the accessory lamps durin...

Page 12: ...S3 is the one hundreds unit for the address the middle switch is the tens unit and the lower switch S1 is the ones unit Addresses may be set from 1 to 501 This unit uses twelve addresses so address 5...

Page 13: ...facturer will void the entire warranty WARRANTY SERVICE CLAIMS Super Vision must issue a Return Material Authorization RMA number for all requests for warranty review To expedite service please contac...

Reviews: