NOTE!
When using a separate control with the heater the temperature sensor with safety
fuse, (which prevents the heater from overheating) must always be installed in the
ceiling directly above the center of the Aries heater even if the control unit’s manual
states otherwise. Installing the sensor above the Aries heater on the wall may cause
over heating of the sauna heater. Do not install the temperature sensor with fuse
closer than 1 meter from the ventilation louvers. Do not place the sensors under
1 m from non-directional air ventilation or not under 0.5 m from a directional air
ventilation, which is directed away from sensors.
DIMMER (OPTIONAL)
It is possible to use any suitable lamp of your choice in the sauna room. However, if the
dimmer feature is present on the control unit and wished to be used, only incandescent
lamp is suitable.
DOOR SENSOR (OPTIONAL)
In other than household use, it is recommended to install door sensor. The door sensor
disables all pre-run operations if the door is opened while the pre-run countdown is
active.
The door sensor also ensures that the door is not open for long periods of time when
the heater is on. If the heater is on and the door is open for more than 15minutes, an
alarm and “DOOR” will be displayed to warn the user. The heater will be switched off
automatically.
NOTE:
If no door sensor is installed, “Door switch” terminals in the Power Controller must be
connected with each other by a jumper wire. See page 16. Note: connection is not
present in the drawing.
FAN (OPTIONAL)
The fan function can only be activated if the fan feature is present on the control unit.
Ensure that the fan motor to be controlled is either shaded pole or permanent split
capacitor motor. The maximum power is 100W with 230 VAC.