Creating a Standby System Project in PG5
Diagnostic
2-4
2
defaults is good for starting the project.
See the
dialog box for more details.
Renaming or deleting devices and files
If you use Project Manager to rename or delete one of the standby devices or
symbol files, then you must open the ‘Standby Configuration’ dialog box and
modify the names there too, Project Manager will not do this automatically. You will
configuration error or warning message
if a device or symbol file is missing.
4. Create the Secondary and Redundant devices
Press OK. The Project Manager will see that the required devices and symbol files
do not exist, and will ask if you want to create them:
Press ‘Yes’ to create the default devices and files. Press ‘No’ if you want to create
these files yourself, or restore, copy or import them from another project. If there
are any files missing, messages will be shown in Project Manager’s “Messages”
window, see
Configuration Error and Warning Messages
.
This message box is also shown if you later rename a device or file, it will always
ask if you want to create a missing device or file.
You can always rename or create the devices and files later if you need to.
5. Configure and download the Device Configuration to the Primary and Sec
-
ondary devices
Open the Device Configurator for the 1-Primary and 2-Secondary devices (CPU0).
Set the S-Bus station number, usually Primary=0 , Secondary=1. Enter the IP
addresses of each device in the “Onboard Communications - Ethernet” slot.
Open the Device Configurator from the 3-Redundant device (CPU1), go to the
“Onboard Communications - Ethernet” slot, and enter the same the IP Addresses
for the Primary and Secondary devices, see
Redundant Device Configuration
.
The new configuration must now be downloaded into the primary and secondary
.