Saia-Burgess Controls AG
User Manual Standby System
│
Document 27-645
│
Edition E
NG 02
│
2017-04-26
Halt and History Messages
Technical Imformation
3-1
3
3
Diagnostics
3.1
Halt and History Messages
If a CPU halts due to a standby system error, a message is placed in the Halt Rea-
son Register and an entry is made in the History log.
Message
HALT Meaning
Red FAIL xxx
Y/N
Caused by Redundancy failure, xxx :=
0 = General error
1 = Redundancy not configured
2 = Out of memory
3 = Media transfer error
4 = CPU “Keep alive” timeout
5 = CPUs have different configurations
6 = Size of media mapping incorrect
7 = No data transfer configured
8 = Incompatible data IDs
9 = Media transfer error 2
Red Media Map FAIL
Y
Redundancy media map configuration error
Red CPU x HALT
Y
CPU x goes into HALT because the other CPU is in HALT
Red CPU REBOOT
Y
CPU rebooted due to CPU communication failure