Saia-Burgess Controls AG
User Manual Standby System
│
Document 27-645
│
Edition E
NG 02
│
2017-04-26
Configuration
Diagnostic
2-16
2
2.5.3
Creating a Default RIO Configuration
A Standby system uses the RIO type PCD3.T668. This type is automatically used
by the RIO Network Configurator if the manager device is a PCD3.M6880. These
RIOs can be programmed to reduce the amount of processing done by the man-
ager device (CPU1). If programmed, they will also run autonomously if communi-
cations with the active manager device has failed.
You can create a default PCD3.T668 configuration using the RIO Network Con
-
figurator (Tools / Default RIO Configuration), and re-use this configuration as a
template for each new RIO. See Project Manager’s help “How to create a RIO
network” for details.
2.5.4
Error and Warning Messages
The following errors may be reported in Project Manager’s “Messages” window
when the standby system configuration is modified, and before a build or down
-
load is done. Errors should be corrected before continuing.
Error Messages
Error 7000: Primary device not found: <device_name>
Error 7000: Secondary device not found: <device_name>
The device does not exist in the project. If the name is incorrect, rename it or
change its name in the Redundancy Configuration. If the device is missing,
create a device with the correct name and the type PCD3.M6880. To create the
device automatically, open the Redundancy Configuration dialog box, press
OK, and answer ‘Yes’ to the “Do you want to create...” message box.
Error 7000: Redundant device not found: <device_name>
The device does not exist in the project. You cannot create a device with the
type PCD3.M6880-CPU1, so open the Redundancy Configuration dialog box,
press OK, and answer ‘Yes’ to the “Do you want to create...” message box.
Error 7001: Primary device is not a PCD3.M6880
Error 7001: Secondary device is not a PCD3.M6880
Error 7001: Redundant device is not a PCD3.M6880-CPU1
The device whose name is defined in the Redundancy Configuration has the
wrong PCD type. If it’s the primary or secondary device, then you can use the
Device Configurator to select the correct type or create a new device with the
right type and change the device name in the Redundancy Configuration. If it’s
a PCD3.M6880-CPU1 device, open the Redundancy Configuration, change the
redundant device name and press OK to create the new device.
Error 7002: Primary device symbol file not defined: <file_path>
Error 7002: Secondary device symbol file not defined: <file_path>
Error 7002: Redundant device symbol file not defined: <file_path>
A global symbol file with the specified name does not exist. Create it manually
or use the Redundancy Configuration dialog to create it for you.
Error 7003: Primary device does not reference Redundant device’s symbol